8. INSTALLER'S TROUBLESHOOTING (
e
d
rror
eSCription
E26
Supply motor (drive over temp)
E32
Exhaust airflow
E33
Exhaust motor (drive over current)
E37
Exhaust motor (drive foc duration)
E38
Exhaust motor (drive speed
feedback)
E39
Exhaust motor (startup)
E34
Exhaust motor (drive over voltage)
E35
Exhaust motor (drive under voltage)
E36
Exhaust motor (drive over temp)
E40
Outside air thermistor
E41
Distribution air thermistor
E42
PCBA thermistor fault
E43
PCBA temperature over limit
E50
Wall control communication lost
E51
Wall control sensor
E60
Protection mode
'
)
Cont
d
STEP 1: Validate if the air exchanger is exposed to ambient temperatures
within the operating limits (see p. 4)
If STEP 1 did not fix the problem, perform STEP 2: Replace the electronic
assembly.
STEP 1: Unplug the unit. Perform a visual inspection of the exhaust damper
system. Clean filters, distribution registers and outside supply hood. Inspect
ducting to ensure it is not squeezed or bent. Plug the unit.
If STEP 1 did not fix the problem, perform STEP 2: Remove ducting of the
supply path. On the LCD screen, select MAX to check if the unit is able to
reach the selected flow. If so, review the ducting path.
If STEP 2 did not fix the problem, perform STEP 3: On the LCD screen, select
the MIN and MAX flow setting values then reset the unit. MAX flow value will
display on the LCD screen. If MAX flow is above desired MAX flow, set MAX
and MIN flows.
If STEP 3 did not fix the problem, perform STEP 4: Replace the exhaust
blower and repeat STEP 3.
If STEP 4 did not fix the problem, perform STEP 5: Replace the electronic
assembly.
STEP 1: Unplug/plug unit.
If STEP 1 did not fix the problem, perform STEP 2: Remove core and clear the
ventilation wheel from any dirt or obstacles.
If STEP 2 did not fix the problem, perform STEP 3: Disconnect J3 (red) and
connect a spare blower system. If it works, replace exhaust blower.
If STEP 3 did not fix the problem, perform STEP 4: Replace the electronic
assembly.
STEP 1: Unplug/plug unit. Under and over voltage may be detected with
severe in-house power supply fluctuation and stop the motor for protection.
If STEP 1 did not fix the problem, perform STEP 2: Replace the electronic
assembly.
STEP 1: Validate if the air exchanger is exposed to ambiant temperatures
within the operating limits (see p. 4)
If STEP 1 did not fix the problem, perform STEP 2: Replace the electronic
assembly.
STEP 1: Check if thermistor is well connected in connector J7A.
If STEP 1 did not fix the problem, perform STEP 2: Disconnect connector J7A
and check if the measured resistance (thermistor connector) is within
5 Kohms to 120 Kohms. If outside the range, replace the thermistor.
If STEP 2 did not fix the problem, perform STEP 3: Replace the electronic
assembly.
STEP 1: Check if thermistor is well connected in connector J7B.
If STEP 1 did not fix the problem, perform STEP 2: Disconnect connector J7B
and check if the measured resistance (thermistor connector) is within
5 Kohms to 120 Kohms. If outside the range, replace the thermistor.
If STEP 2 did not fix the problem, perform STEP 3: Replace the electronic
assembly.
STEP 1: Replace the electronic assembly.
STEP 1: Validate if the air exchanger is exposed to ambiant temperatures
within the operating limits (see p. 4)
If STEP 1 did not fix the problem, perform STEP 2: Replace the electronic assembly.
STEP 1: Unplug unit, inspect wires, plug unit.
If STEP 1 did not fix the problem, perform STEP 2: Remove wall control from
the wall installation and test with a short cable. If it works, bring a new cable
to the wall installation location.
If STEP 2 did not fix the problem, perform STEP 3: Test the air exchanger with
a spare wall control. If it works, replace the wall control.
If STEP 3 did not fix the problem, perform STEP 4: Replace the electronic
assembly.
STEP 1: Unplug unit, inspect wires, plug unit.
If STEP 1 did not fix the problem, perform STEP 2: Replace the wall control.
STEP 1: Perform general inspection of the unit (dampers, core, filters).
21