Read this manual attentively before starting up the unit. Do
not throw it away. Keep it in your files for future reference.
Improper installation or attachment of equipment or
accessories could result in electric shock, short-circuit,
leaks, fire or other damage to the equipment. Be sure only
to use accessories made by Daikin which are specifically
designed for the use with the equipment and have them
installed by a professional.
If unsure of installation procedures or use, always contact
your Daikin dealer for advice and information.
The optional EEH (electric heater kit) cannot be mounted on
units which are set up for 2-pipe systems with 4-row coil and
4-pipe systems.
B
efore installation
Installation and maintenance should be carried out by technical
personnel qualified for this type of machine, in compliance with current
safety regulations.
When receiving the unit please check its state, verifying if any damage
occurred during the transport.
Refer to the relevant technical sheets for installation and use of
possible accessories.
Identify model and version of the unit from the indications stated on the
carton package.
U
se and operating limits
Daikin shall not be held liable
- if the unit has been installed by non-qualified personnel,
- if the unit has been used improperly,
- if the unit has been used under conditions that are not permitted,
- if maintenance operations specified in this manual have not been
carried out,
- if non original spare parts have been used.
Keep the unit in its packaging until it is ready to be installed, to prevent
dust getting inside.
Operating limits are shown here below; all other uses are considered
improper:
thermal fluid: water/glycol
!
water temperature: 5°C~95°C
!
maximum operating pressure: 10 bar
!
air temperature: 5°C~43°C
!
nominal power supply voltage: 230V - 50 Hz
!
Selection of location:
do not install the unit in rooms where inflammable gases are
!
present
do not let water spray directly on the unit;
!
install the unit on ceilings or walls that bear its weight. Leave
!
enough space all around for proper operation and maintenance of
the unit, taking into account all installed optional accessories.
never place the heating unit immediately under an electric
!
plug-socket.
Installation and operation manual
1
Fan coil units
d
imensions (See figure 1)
1
Clear space for hydraulic connections
2
Slots for wall/ceiling mounting 9 x 20 mm
3
Clear space for electric connections
4
Hydraulic connections (4 DF = 4 pipe system)
5
Condensate drainage for vertical installation
6
Air outlet for concealed models
7
Air suction for concealed models
8
Condensate draining for horizontal installation
9
Air outlet
10
Air inlet
Indications applicable to units with hydraulic connections on the left side; in case of right side
(*)
connections the indications for "clear space" are reversed.
i
nstallation
Before installing the fan coil, ensure that:
- The place of installation has sufficient space for
containing the device and for performing installation and
maintenance (respect spaces fig. point 2).
- The air inlet and delivery are not obstructed.
- The hydraulic connections are positioned and
dimensioned as requested by the device (fig.1).
- The electric power supply line has the features
requested on the fan coil's data plate.
Remove the cabinet, where existing, by unscrewing the 4 fastening
screws reachable through the lifted side doors (see figure 2). In case of
FWL and FWR versions, also unscrew the 2 screws on the front panel.
Install the basic unit onto the wall/ceiling using the 4 mounting slots
and the supplied anchor screws, keeping the unit at least 100 mm
above the floor for a proper air suction and an easy pulling out of the
filter in case of FWV, FWZ, FWM and FWS models. In case of ceiling
models FWM, FWS, FWL and FWR verify that the installation height
corresponds to what is specified in figure 3, in order to avoid excessive
hot air stratification in the upper part of the room; in case of greater
installation heights we suggest to proceed with the back suction from
the lower part of the room. The installation heights refer to the
maximum running speed.
Carry out the hydraulic connections to the heat exchanger and in case
of cooling operation, to the water drainage system.
In case of cooling applications, make sure to insulate all field installed
piping and fittings as to avoid condensate dripping on the floor. Non
insulated piping can cause water damage!
We suggest to provide for the water inlet from the bottom side of the
heat exchanger and the outlet on the upper side.
For a better water drainage lean the drain pipe downwards at least
3þcm/m avoiding loops or narrowing on its way.
Installation and
operation manual
(*)
(*)
FWV+FWZ+FWL+FWR+FWM+FWS
Fan coil units
4PW17548-3