Problem
Cell Probe Alarm
The display shows the
following message:
ALL CellSensor
The buzzer is active.
Evaporator Probe Alarm
The display shows the
following message:
ALL EvapSensor
The buzzer is active.
Problem
Evaporator High
Temperature Alarm
The display shows the
following message:
ALL High TEvap
The buzzer is active.
The temperature detected
by the evaporator probe
has exceeded the limit
value (60°C)
Humidity Probe Alarm
The display shows the
following message:
ALL HUM Sensor
The buzzer is active.
Safety Thermostat
Vapour Generator Alarm
The display shows the
following message:
ALL Thermostat
The buzzer is active.
Effects
All cycles in course are
blocked and all outlets
deactivated.
The buzzer can be
silenced pressing any
key
All cycles in course are
blocked and all outlets
deactivated.
The buzzer can be
silenced pressing any
key
Effects
All cycles in course are
blocked and all outlets
deactivated.
The buzzer can be
silenced pressing any
key.
All cycles in course are
blocked and all outlets
deactivated.
The buzzer can be
silenced pressing any
key.
All cycles in course are
blocked and all outlets
deactivated.
The buzzer can be
silenced pressing any
key.
21
Causes
Cell probe fault
Evaporator probe fault
Causes
Evaporator fan at a
standstill.
Resistances always
inserted.
Humidity probe fault.
Water connection not
completed.
Defective water filling
valve.
ENGLISH
Solutions
Replace the cell probe
Contact the after-
sales centre.
When the error has
disappeared, the cycle
restarts.
Replace the evaporator
probe
Contact the after-
sales centre.
When the error has
disappeared, the cycle
restarts.
Solutions
Replace the evaporator fan
Contact the after-
sales centre.
When the error has
disappeared, the cycle
restarts.
Verify the connection of the
heating resistances
Contact the after-
sales centre.
When the error has
disappeared, the cycle
restarts.
Replace the humidity
Contact the
probe
after-sales centre.
When the error has
disappeared, the cycle
restarts.
Connect the boiler to the
water network using the
pipes supplied.
When the error has
disappeared, the cycle
restarts.
Contact the after-
sales centre.