Preparing For Commissioning - Festo VPPM C1 LCD Serie Notice D'utilisation

Manodétendeur proportionnel
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 25
PIN Cable
Port designations
1)
colour
Voltage variants
type
VPPM-...-V1...C1
1
White
Digital input D1
(WH)
2
Brown
+24 V DC power supply
(BN)
3
Green
Analogue input W- (- setpoint value)
(GN)
4
Yellow
Analogue input W+
(YE)
(+ setpoint value)
0 ... 10 V
5
Grey (GY)
Digital input D2
6
Pink (PK)
Analogue output X (actual value)
7
Blue (BU)
GND Supply earth
2)
8
Red (RD)
Digital output D3
PE braided screen on thread
1) Using the connector socket with cable as per "Accessories". The max. tightening torque is 0.5 Nm.
Fig. 12
VPPM-... circuit diagrams Switching output
PNP
2
BN
P
+24 V
RD
8
R
L
0 V
7
BU
PNP
Fig. 13
6
Commissioning
6.1 Fast commissioning with factory setting
The VPPM-...C1 is delivered with the following factory setting:
• Switching behaviour:
• Switching point
The switching point is only active when a comparator is selected (threshold
value or window comparator).
• Hysteresis:
• Switching characteristic:
If you wish to use the factory setting but define a different switching point for Out,
proceed as follows;
Note
When the operating voltage is switched on, the VPPM-...C1 will automatically be
in the RUN mode (basic setting). If you are not sure whether the VPPM-...C1 is in
the RUN mode, hold the EDIT button down for 3 s. The VPPM-...C1 will then be in
the RUN mode. You can set switching points manually.
You can set a switching point manually as follows:
1. In order to activate the EDIT mode, press the EDIT button. [Out] flashes.
2. Press the EDIT button twice. SP flashes.
3. Edit the threshold value shown with the UP or DOWN button.
4. Hold the EDIT button pressed down for 3 s. The VPPM-...C1 will then be in the
RUN mode.

6.2 Preparing for commissioning

Note
• Make sure that the VPPM-...C1 is not subjected to high-frequency irradiation
(e.g. by radio sets, mobile telephones or other devices which emit interfer-
ence). In this way you will avoid increased tolerances in the output pressure
(EMC specifications
Technical data).
• The VPPM-...C1 interprets setpoint value signals which are smaller than 1 %
full scale as 0 V (
Output pressure range table). In this case the working
pressure will be set to the ambient pressure.
During the initial start-up the RUN mode will appear. This shows the current
measured value. By briefly pressing the DOWN button you can display the setpoint
value.
The RUN mode can be accessed from other modes:
– Press the EDIT button down for 3 s.
– after expiration of a monitoring time (Timeout
Proceed with preparation for commissioning as follows:
• Switch on the operating voltage. The VPPM-...C1 will then be in the RUN mode.
• Check the functioning of the VPPM-...C1
Observe the following points for setting the control characteristics via digital in-
puts or display:
Plug M12
Current variants
type
VPPM-...-A4...C1
2
3
Analogue input W+
(+ setpoint value)
4 ... 20 mA
4
NPN
2
BN
P
RD
8
R
7
BU
NPN
value comparator setting
40 % FS (full scale)
0.5 % FS
NO (normally open contact)
"Menu structure" section)
Note
Selection of the control characteristics via digital inputs D1 and D2 takes priority
over the factory parameter sets in VPPM-...C1.
• If you wish to select the control characteristics via the factory parameters,
8
1
make sure that a logic 0 signal is present at digital inputs D1 and D2.
• You can select the desired factory parameter set in the EDIT menu on the
VPPM-...C1 (
is preselected at the factory.
7
• If you wish to preselect the control characteristics via the digital inputs, activate
the following signals at digital inputs D1 and D2:
Parameter set
5
6
1
2
3
...
1) 1 = 24 V DC / 0 = 0 V DC
Fig. 14
+24 V
6.3 Symbols on the display of the VPPM-...C1
L
0 V
Menu level
Out
In
Force
Set...
SPEC
1) Depends on the variant of the VPPM-...C1
2) Depends on unit set in SPEC menu
Fig. 15
Fig. 25). Parameter set Set2 (universal control characteristics)
Control characteristics
Fast control reaction
Universal control reaction
(factory setting)
Precise control reaction
Select parameter set via display of the
VPPM-...C1
Symbol
Description
Switching output set/not set
/
[Out]
Switching output
Threshold value comparator
[SP]
Switching point
Window comparator
[SP max]
Upper switching point
[SP min]
Lower switching point
SP.O.
SetPoint OK
[HY]
Hysteresis
[NO]
Contact (normally open)
[NC]
Contact (normally closed)
[In]
Input
[min]
Lower pressure value
[max]
Upper pressure value
1)
[mA] or [V]
,
Units of the input
[%],
2)
[bar], [psi], [kPa]
[Force]
Manual setpoint specification
[Set 1], [Set 2], [Set 3]
Factory parameter sets
[SPEC]
Special menu
[LOCK]
Security code active (blocked against unautho-
rised programming)
[kPa], [psi], [bar]
Units of pressure, can be switched
Pressure display as bar chart
Input D1
Input D2
1)
1)
PIN 1
PIN 5
1
0
0
1
1
1
0
0