Troubleshooting
3.4
During use
3.4.1
General notes
After powering-up, the flame detector requires almost no attention to
function properly, but the following should be noted:
Do not expose the flame detector to radiation of any kind unless
required for testing purposes.
Do not expose the Dräger Flame 2100 to a UV radiation source
(for example: welding, sparks, electronic arc), as this will result in
a false alarm.
Do not open the detector housing while power is applied - there is
a risk of ignition of hazardous atmospheres.
Do not open the electronic compartment. This part should be kept
closed always and only opened in the factory. Opening the
electronic component side invalidates the warranty.
Only access the wiring compartment to wire or remove the
detector or access RS485 terminals for maintenance.
3.4.2
Manual reset
Note: Most detectors are used in the non-latching alarm mode. Only
perform a reset when the latching alarm option has been programmed.
Disconnect power (terminal number 1 or terminal number 2).
or
Initiate a manual BIT (Dräger Flame 2100/2350 only).
18
All manuals and user guides at all-guides.com
4
Problem
Status LED off
Fault relay at N.O.
0-20 mA output at
0 mA
Status LED flashes
yellow at 4 Hz
Fault relay at N.O.
0-20 mA output at
0 mA
Status LED flashes
yellow at 4 Hz
Fault relay at N.O.
0-20 mA output at
2 mA
Status LED lights
constantly red
Troubleshooting
Cause
Flame detector not
energized
Detector fault
Low voltage
Faulty
detector
BIT fault
Faulty
detector
If no fire exists, the
alarm is latched.
Corrective action
Check that the
correct power is
applied
to
the
flame detector.
Check
power
polarity.
Check wiring in
the
flame
detector.
Send the flame
detector to Dräger
for repairs.
Check the voltage
at
the
flame
flame
detector; verify at
least 24 V at the
detector terminal.
Send the flame
detector to Dräger
for repairs.
Clean
detector
flame
window.
Repower
the
flame detector.
Send the flame
detector to Dräger
for repairs.
Reset the flame
detector.