Lowara GXS20 Notice Pour L'installation, L'utilisation Et L'entretien page 15

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 22
Figure 1 represents front of single-phase panel
Pos
Description fig. 1
1
Main switch
2
Red dry running warning light
3
Green power warning light
4
Manual-Off-Automatic pump selector
switch
5
Green pump running indicator light
GMD20,GMY20 Three-Phase Version
The three-phase version has a QMD20,QMY20 control panel:
- Automatic sequential pump regulation with low-pressure control from two pressure switches.
- Cyclic changeover of first pump to be started.
- Changeover lock selector switch.
- Delay to prevent simultaneous start-up.
- Short-circuit and overload protection via an automatic switch.
- Dry running protection via a pressure switch or float switch or level sensors with sensitivity adjustment
(accessory electrodes not included).
- Dry running protection cut-in timer.
- Shut-down delay timers on both pumps
- Output for dry contact relay card (accessory)
- Electromechanical selector switches for Automatic-Off-Manual operation (Inside panel)
Figure 2 represents front of three-phase panel
Pos
Description fig. 2
1
Main switch
2
Green power warning light
3
Red dry running warning light
4
Red overload warning light
5
Green pump running indicator light
6
Automatic mode pushbutton
7
Manual mode pushbutton
8
Green automatic mode indicator light
9
Red manual mode indicator light
10
Manual mode on/off pushbuttons
Symbol
POWER
Symbol
AUT
MAN
0/1
en
15