Toshiba MMU-AP0094HP-E Manuel D'installation page 49

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 6
+001114119501.book Page 48 Wednesday, October 17, 2012 8:23 PM
Check code
Outdoor unit 7-segment display
Wired remote
controller display
Auxiliary code
F01
F02
F03
F04
F04
F05
F05
01:TE1 sensor
F06
F06
02:TE2 sensor
F07
F07
F08
F08
F10
F12
F12
01:Comp. 1 side
F13
F13
02:Comp. 2 side
03:Comp. 3 side
F15
F15
F16
F16
F22
F22
F23
F23
F24
F24
F29
F31
F31
01:Comp. 1 side
H01
H01
02:Comp. 2 side
03:Comp. 3 side
01:Comp. 1 side
H02
H02
02:Comp. 2 side
03:Comp. 3 side
01:Comp. 1 side
H03
H03
02:Comp. 2 side
03:Comp. 3 side
H04
H04
H05
H05
H06
H06
H07
H07
01:TK1 sensor error
02:TK2 sensor error
H08
H08
03:TK3 sensor error
04:TK4 sensor error
05:TK5 sensor error
H14
H14
H15
H15
01:TK1 oil circuit system error
02:TK2 oil circuit system error
H16
H16
03:TK3 oil circuit system error
04:TK4 oil circuit system error
05:TK5 oil circuit system error
H25
H25
L03
95-EN
Wireless remote controller
Sensor block display of receiving unit
AI-NET central
control display
Operation
0F
0d
93
19
A1
18
18
1b
OC
A2
43
18
43
B2
43
43
12
1C
IF
1d
17
44
20
d7
d4
44
d7
96
Timer
Ready
Flash
ALT
Indoor unit TCJ sensor error
ALT
Indoor unit TC2 sensor error
ALT
Indoor unit TC1 sensor error
ALT
TD1 sensor error
ALT
TD2 sensor error
TE1 sensor error
ALT
TE2 sensor error
ALT
TL sensor error
ALT
TO sensor error
ALT
Indoor unit TA sensor error
ALT
TS1 sensor error
ALT
TH sensor error
ALT
Outdoor unit temp. sensor miscabling (TE, TL)
ALT
Outdoor unit pressure sensor miscabling (Pd, Ps)
ALT
TD3 sensor error
ALT
Ps sensor error
ALT
Pd sensor error
SIM
Indoor unit other error
SIM
Indoor unit EEPROM error
Compressor break down
Compressor trouble (lock)
Current detect circuit system error
Comp. 1 case thermo operation
TD1 sensor miswiring
Low pressure protective operation
Oil level down detective protection
Oil level detective temp sensor error
Comp. 2 case thermo operation
TD2 sensor miswiring
Oil level detective circuit error
TD3 sensor miswiring
SIM
Indoor unit centre unit duplicated
– 48 –
Check code name
Judging device
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
I/F
I/F
I/F
I/F
I/F
I/F
IPDU
I/F
I/F
I/F
I/F
I/F
I/F
IPDU
IPDU
IPDU
I/F
I/F
I/F
I/F
I/F
I/F
I/F
I/F
I/F
96-EN

Publicité

Table des Matières
loading

Table des Matières