6. Specifications

MODEL
CAPACITY*
INPUT
Low Line Transfer
Voltage
Low Line Comeback
Range
High Line Transfer
High Line Comeback
Frequency Range
Phase
Power Factor
OUTPUT
Output voltage
AC Voltage Regulation
(Batt. Mode)
Frequency Range
(Synchronized Range)
Frequency Range (Batt. Mode)
Overload
Current Crest Ratio
Harmonic Distortion
AC Mode to Batt. Mode
Transfer
Time
Inverter to Bypass
Waveform (Batt. Mode)
EFFICIENCY
AC Mode
Battery Mode
BATTERY
Battery Type
Numbers
Standard
Recharge Time
Model
Charging Current
Charging Voltage
Battery Type & Numbers
Long-run
Charging Current
Model
Charging Voltage
PHYSICAL
Dimension, D X W X H
Net Weight (kgs)
ENVIRONMENT
Operation Humidity
Noise Level
MANAGEMENT
Smart RS-232 or USB
Optional SNMP
* Reduce capacity to 60% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 208VAC.
**Product specifications are subject to change without further notice.
INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
41
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 11 10 AA 59 203 04
All manuals and user guides at all-guides.com
E4 LCD 1000 (S)
E4 LCD 1500 (S)
1000 VA / 800 W
1500 VA / 1200 W
160/140/120/110 VAC ± 5 % or 80/70/60/50 VAC ± 5 %
( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
≧ 0.99 @ 220-230 VAC (input voltage)
208/220/230/240VAC or 110/115/120/127 VAC
110%-130%: UPS shuts down in 30 seconds at battery mode or transfers to bypass
>130%: UPS shuts down immediately at battery mode or transfer to bypass mode when
≦ 3 % THD (Linear Load)
≦ 6 % THD (Non-linear Load)
~ 85%
12 V / 7 AH
3
4 hours to recover to 90% capacity (Typical)
41.0 VDC ± 1%
Depending on the capacity of external batteries
41.0 VDC ± 1%
397 X 145 X 220 (mm)
13
7
20-90 % RH @ 0- 40°C (non-condensing)
Supports Windows®2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix and MAC
Power management from SNMP manager and web browser
E4 LCD 2000 (S)
2000 VA / 1600 W
175 VAC ± 5 % or 85 VAC ± 5 %
300 VAC ± 5 % or 150 VAC ± 5 %
290 VAC ± 5 % or 145 VAC ± 5 %
40Hz ~ 70 Hz
Single phase with ground
± 3%
47 ~ 53 Hz or 57 ~ 63 Hz
50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
100%~110%: audible warning
mode when the utility is normal.
the utility is normal.
3:1
≦ 4 % THD (Linear Load)
≦ 7 % THD (Non-linear Load)
Zero
4 ms (Typical)
Pure Sinewave
~ 83%
12 V / 9 AH
12 V / 7 AH
3
1.0 A(max.)
4.0 A or 8.0 A(max.)
14
7
26
Less than 45dBA @ 1 Meter
E4 LCD 3000 (S)
3000 VA / 2400 W
~ 88%
12 V / 9 AH
6
6
82.1 VDC ±1%
82.1 VDC ±1%
421 X 190 X 318 (mm)
13
28
13