ABB ACS800 Manuel D'installation page 13

0,55 à 110 kw, 0,75 à 150 hp
Masquer les pouces Voir aussi pour ACS800:
Table des Matières

Publicité

Update Notice
The notice concerns the following ACS800-01/U1
Hardware Manuals:
Code
Revision
3AFE64526146
F
3AFE64526120
F
3AFE64526197
F
3AFE64526502
F
3AFE64526545
F
3AFE64526596
F
3AFE64526618
F
3AFE64526634
F
3AFE64526669
F
3AFE64526693
F
IEC data
Ratings
ACS800-01 size
Nominal
ratings
I
cont.max
A
Three-phase supply voltage 380 V, 400 V or 415 V
-0075-3
145
-0135-3
225
-0165-3
260
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
-0105-5
145
-0165-5
225
-0205-5
260
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or 690 V
-0145-7
134
-0175-7
166
-0205-7
190
Language
Danish
DA
German
DE
Spanish
ES
Finnish
FI
French
FR
Italian
IT
Dutch
NL
Portuguese
PT
Russian
RU
Swedish
SV
Light-overload
No-
overload
use
use
I
I
P
max
cont.max
2N
kW
A
A
170
75
141
326
110
220
326
132
254
170
90
141
326
132
220
326
160
254
245
132
125
245
160
155
245
160
180
Code: 3AFE68835810 Rev C
Valid: from 25.6.2007 until the release of Rev H of the manual
Contents: the data of new drive types which is not yet updated
to the manual, installation of optional Prevention of
Unexpected Start (+Q950).
A summary of the updates is given below.
- NEW: drive types ACS800-01-0075-3, ACS800-01-0135-3,
ACS800-01-0105-5, ACS800-01-0165-3, ACS800-01-0165-5,
ACS800-01-0205-5, ACS800-01-0145-7, ACS800-01-0175-7
and ACS800-01-0205-7.
Heavy-duty use
P
I
P
N
2hd
kW
A
kW
75
100
45
110
163
90
132
215
110
90
100
55
132
163
110
160
215
132
110
95
90
132
131
110
160
147
132
Frame
Air flow
size
hd
3
m
/h
R5
405
R6
405
R6
405
R5
405
R6
405
R6
405
R6
405
R6
405
R6
405
PDM code: 00096931-J
Update Notice
1
Heat
dissipation
W
1440
2810
3260
2150
3260
3800
2660
3470
4180

Publicité