Manually Starting/Stopping Tank Leak Tests
Use this screen to manually start or stop a Tank Leak Test.
Manual Test Start/Stop Screen
Legend for numbered boxes
5
Test Method [129] - Select Single Tank or All Tanks.
Touch the Down Arrow button to the right of the
window and enter the desired choice.
6
Test Control [130] - Select Timed Duration or Manual
Stop (test runs until you stop it, or for 24 hours,
whichever comes first). Touch the Down Arrow button
to the right of the window and enter the desired
choice.
7
Test Rate [112] - Select a leak test rate of 0.2 gph
(0.76 lph) (default) or 0.1 gph (0.38 lph). The 0.1 gph
(0.38 lph) rate requires a Mag 1 Probe. Touch the
Down Arrow button to the right of the window and
enter the desired choice.
8
Test Duration [114] - Select a test duration of from 0 to
24 hours. There is a minimum duration of two hours for
0.2 gph (0.76 lph) tests and three hours for 0.1 gph
(0.38 lph) tests. Default is 2 hours.
Note: this window only appears if you selected Timed
Duration in the Test Control window. Touch the Down
48
01-01-2000
ALL FUNCTIONS NORMAL
12:00 AM
MANUAL TANK TEST
1
[129]
2
[130]
3
[112]
4
[114]
1
2
TANK 1
0.76 LPH
3
4
5
Arrow button to the right of the window and
enter the desired choice.
9
Test Start button - Touch this button to begin
the test.
10
Test Stop button - Touch this button to stop a
tank leak test.
5
6
6