TLS2 Setup
[109-111] Tank Limits Setup Screen 3
Legend for numbered boxes
This screen concludes Tank Alarm Limit setup.
1
Gross Test Fail [109] - Gross Test Fail allows you to
disable or enable an alarm that triggers if a 3 gph (11.3
lph) leak test fails. Choices are Alarm Enabled or
Disabled. Default is Disabled. Touch the Down Arrow
button to the right of the window and enter the desired
choice.
2
Periodic Test Fail [110] - Periodic Test Fail allows you to
disable or enable an alarm that triggers if a 0.2 gph
(0.76 lph) leak test fails. Choices are Alarm Enabled or
Disabled. Default is Disabled. Touch the Down Arrow
button to the right of the window and enter the desired
choice.
3
Annual Test Fail [111] - Annual Test Fail alarms when
an annual leak test has not passed. Choices are Alarm
Enabled or Disabled. Default is Disabled. Touch the
Down Arrow button to the right of the window and enter
the desired choice.
01-01-2000
ALL FUNCTIONS NORMAL
12:00 AM
1
[109]
2
[110]
3
[111]
1
2
3
4
5
[109-111] Tank Limits Setup Screen 3