8. ERROR MESSAGES

Message
Meaning
Water
Temperature is
Unknown
A potential freeze condition has been
Possible
detected, or the Aux Freeze Switch has
freezing
closed.
condition
The water is too
The system has detected a spa water
temp of 110°F (43.3°C) or more, and spa
hot – M029
functions are disabled.
The water level
This message can only appear on a system
that uses a water level sensor. It appears
is too low
whenever the water level get too low (or
the water level sensor is disconnected)
There may not be enough water flow
The water flow
through the heater to carry the heat away
is low – M016
from the heating element.
There is not enough water flow through
The water flow
the heater to carry the heat away from the
has failed –
heating element and the heater has been
M017
disabled.
The heater may
Possible dry heater, or not enough water in
the heater to start it. The spa is shut down
be dry – M028
for 15 min.
The heater is
There is not enough water in the heater to
start it. The spa is shut down.
dry – M027
The heater is
One of the water temp sensors has
detected 118°f (47.8°C) in the heater and the
too hot – M030
spa is shut down.
Flow-Related
Checks
Sensors are out
The temperature sensors MAY be out of
sync by 3°F.
of sync – M015
Action required
After the pump has been running for 1 minute, the
temperature will be displayed.
All water devices are activated. In some cases, pumps
may turn on and off and the heater may operate
during Freeze Protection.
This is an operational message, not an error indication.
System will auto reset when the spa water temp
is below 108°F (42.2°C). Check for extended pump
operation or high ambient temp.
Automatically disappears when the water level is
adequate. Pumps and the heater turn OFF when this
message appears.
Heater start up will begin again after about 1 min.
See: **.
See: **.
See: **.
After the problem has been resolved, you must reset
the message to restart heater start up.
See: **.
You must reset the message when water is below
108°f (42.2°C).
See: **.
Check for low water level, suction flow restrictions,
closed valves, trapped air, too many closed jets and
pump prime.
Call for Service if this message does not disappear
within a few minutes.