Switchpoint - sauter EGH102F901 Notice D'instruction

De condensation avec sonde déportée, avec sortie en tout ou rien
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

G
EGH102F901
Schematic diagram
LED
Short LED pulses =
relay active =>
below switchpoint
Long LED pulses =
relay inactive =>
above switchpoint
1 2 3
Connecting scheme
Power supply
AC 24V~
0V
DC 15-36V = GND
SUPPLY VOLTAGE :
For operating voltage reverse polarity protection, a one-way rectifier or
reverse polarity protection diode is integrated in this device variant.
This internal one-way rectifier also allows operating 0 - 10 V devices on AC
supply voltage.
The output signal is to be tapped by a measuring instrument. Output
voltage is measured her against zero potential (O V) of the input voltage!
When this device is operated on DC supply voltage , the operating voltage
input UB+ is to be used for 15...36 V DC supply and UB – or GND for
ground wire!

Switchpoint

ca. 93% r.H.
13 11 12
Individual operation
Circuitry
V
8
Connecting diagram
(no condensation)
r.H. < 93 %
UB+ supply voltage 24V AC/DC
1
2
free
3
GND
Normally open contact
13
(no dew)
11
Breaker
12
(dew)
Connecting diagram
(condensation)
r.H. > 93 %
UB+ supply voltage 24V AC/DC
1
2
free
3
GND
Normally open contact
13
(no dew)
11
Breaker
12
(dew)
Connecting scheme
Power supply
AC 24V~
0V
DC 15-36V = GND
When several devices are supplied by one 24 V AC voltage supply, it is to
be ensured that all "positive" operating voltage input terminals (+) of the
field devices are connected with each other and all "negative" operating
voltage input terminals (–) (= reference potential) are connected together
(in-phase connection of field devices). All outputs of field devices must be
referenced to the same potential!
In case of reversed polarity at one field device, a supply voltage short-
circuit would be caused by that device. The consequential short-circuit
current flowing through this field device may cause damage to it.
Therefore, pay attention to correct wiring!
Rev. 2022 - V18
changeover
(24 V)
changeover
(24 V)
Parallel operation
Circuitry
Circuitry