All burners factory tested at 400 V 50 Hz three-phase for motors and 230 V 50 Hz monophase with neutral for auxi-
liary equipment. If mains supply is 230 V 50 Hz threephase withuot neutral, change position of connectors on burner
as in fig. Protect burner supply line with safety fuses and any other devices required by safety standards obtaining in the
country in question.
Once connected the burner to the gas pipeline, it is necessary to control that this last is perfectly sealed. Also verify that
the chimney is not obstructed. Open the gas cock and carefully bleed the piping through the pressure gauge connector,
then check the pressure value trough a suitable gauge. Power on the system and adjust the thermostats to the desired
temperature. When thermostats close, the sealing control device runs a seal test of valves; at the end of the test the bur-
ner will be enabled to run the start-up sequence.
To be supplied by the installer
141
143
Gas
To be supplied by the installer
Before starting the burner, make sure it is mounted correctly. Then check connections are correct according to the dia-
gram and piping is appropriate to the system. Before connecting the burner to the electricity supply, make sure voltage
corresponds to burner plate data. The connection diagram and start-up cycle are shown separa-
tely. For wiring from control box to burner, see the enclosed connection diagram. Pay particular
attention to neutral and phase connections : never exchange them!. Vent air and impurities of
gas pipe. Check gas pressure conforms to the limits stated on the burner plate when connecting
a master gauge to the test port provided on the burner. Blower motor starts and pre-purging
begins. Since pre-purging has to be carried out with the max. air delivery, the burner control
circuit turns the air damper to the max. delivery position by the air servocontrol in approximately 30 seconds time.
When the servocontrol is fully open, a signal to the electronic control unit starts the 66 seconds (36 s. LFL 1.333)
seconds pre-purge cycle. At the end of the prepurging time, the air servocontrol gets to the Low Flame position so that
burner ignition is ensured at min. output. Simultaneously the ignition transformer receives voltage and after 3 seconds
(pre-ignition) opens the pilot gas valve. Fuel flows to the combustion head and ignites. Two seconds after pilot gas val-
ves have opened, the ignition transformer is excluded from the circuit. In case of no ignition the burner goes to lock-
out within two seconds. After 6 sec. open the working gas valve, governed by the gas firing butterfly valve.Now the bur-
ner is operating at the min. firing rate (about 30% of the max. firing rate). The air servocontrol runs at the Low Flame
position and in case the temperature control has to be set at the max. output it goes to a fully open position of air dam-
per and butterfly valve. During the burner-off periods the air damper closes up fully.

ELECTRICAL CONNECTIONS

CONNECTION TO THE GAS PIPELINE
CONNECTION DIAGRAM FOR BURNERS WITH SEPARATE PILOT
CONNECTION DIAGRAM FOR BURNERS WITH SEPARATE PILOT
(gas train Landis VGD...)
(GAS TRAIN LANDIS VGD...)
107
155
170
313
144
142
151
OPERATION OF BURNER WITH GAS
160
314
150
120
Air
M
349
18
100 Burner
100
Burner
107
107 Pilot gas filter/governor
Pilot gas filter/governor
120
Air damper
120 Air damper
141
Ball valve
141 Ball valve
142
Gas filter
142 Gas filter
143
Antivibration coupling
143 Antivibration coupling
144
Gas governor
144 Gas governor
150
Batterfly valve
150 Batterfly valve
151
Gas train Landis VGD....
151 Gas train Landis VGD....
155
Pilot gas train
155 Pilot gas train
160
Kit tightness control (optional)
160 Kit tightness control (optional)
170
Kit tightness control for pilot gas valve (optional)
170 Kit tightness control for pilot gas valve (optional)
313
Min.gas pressure switch
313 Min.gas pressure switch
314
Max.gas pressure switch (optional)
314 Max.gas pressure switch (optional)
349
Air/gas damper motor
349 Air/gas damper motor
100
1
0 - STOP
LIGHT-OIL
1 - GASOLIO
2 - GAS
0
2

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Multicalor 800.1Multicalor 1000.1Multicalor 1200.1

Table des Matières