Mounting Of The Boiler; Electrical Connections; Combustion Chamber - Ecoflam MAX GAS 350 P Mode D'emploi

Masquer les pouces Voir aussi pour MAX GAS 350 P:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 28
420010400701 Max Gas 350 - 500 P/P AB
EN
All burners factory tested at 220V 60 Hz monophase (Max Gas 350) or 380 V 60 Hz three-phase (Max Gas 500) for
motors and 220V 60 Hz monophase for auxiliary equipment. If mains supply is 220 V 60 Hz threephase withuot neu-
tral, change position of connectors on burner as in fig. Protect burner supply line with safety fuses and any other devi-
ces required by safety standards obtaining in the country in question.
Once connected the burner to the gas pipeline, it is necessary to control that this last is perfectly sealed. Also verify that
the chimney is not obstructed. Open the gas cock and carefully bleed the piping through the pressure gauge connector,
then check the pressure value trough a suitable gauge. Power on the system and adjust the thermostats to the desired
temperature. When thermostats close, the sealing control device runs a seal test of valves; at the end of the test the bur-
ner will be enabled to run the start-up sequence.
4,0
3,0
2,0
1,0
0,6
0,5
0,4
d=0,3
0,3
d=0,225
0,2
0,1
12
24
(a)
kW
d = diamètre chambre de combustion
MOUNTING TO THE BOILER

ELECTRICAL CONNECTIONS

CONNECTION TO THE GAS PIPELINE

COMBUSTION CHAMBER

d=0,6
d=0,5
d=0,4
40
70 100
190
480
The burners have been certified in combustion
d=0,8
chambers according to EN 676 standards.
d=0,7
Consult the burner manufacturer if the combu-
stion chamber of the boiler in which the burner
is to be installed has smaller dimensions.
Installation must be carried out in com-
1200
2450
16
pliance with the local provisions

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Max gas 350 p abMax gas 500 pMax gas 500 p ab

Table des Matières