Position Of Electrodes - Ecoflam BLU 1700.1-20 PAB Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

420010350800 Blu 1700.1÷2000.1 P AB
EN
The firing head position adjustment is made in order to obtain the best combustion efficiency. When used with mini-
mum outputs the firing head is adjusted in rear position. With high output, the firing head is adjusted in forward posi-
tion. Adjustment:
- Loosen screw A through a suitable Allen key. - By a screwdriver act on the hex. head screw B until is reached the desi-
red position. - Tighten screw A
+
B
Ionization probe
ADJUSTMENT OF GAS MINIMUM PRESSURE SWITCH
Unscrew off and remove cover M. - Set regulator N to a value equal to 60% of gas nominal feed
pressure (i.e. for nat. gas nom. pressure = 20 mbar, set regulator to a value of 12 mbar; for
L.P.G. nom. pressure of G30/G31- 30/37 mbar, set regulator to a value of 18 mbar).Screw
up cover M
DJUSTMENT OF THE AIR PRESSURE SWITCH
Unscrew screws A and B and remove cover C.- Set the pressure switch to the minimum by
turning regulator D to position 1.
- Start the burner and keep in low flame running, while checking that combustion is correct.
Through a small cardboard, progressively obstruct the air intake until to obtain a CO2 increase
of 0,5÷0,8% or else, if a pressure gauge is available, connected to pressure port E, until rea-
ching a pressure drop of 1 mbar (10 mm of W.G.). - Slowly increase the adjustment value
of the air pressure switch until to have the burner lockout. Remove the obstruction from
the air intake, screw on the cover C and start the burner by pressing the control box rearm
button.
Note: The pressure measured at pressure port E must be within the limits of the pressure switch working
range. If not, loose the locking nut of screw F and gradually turn the same: clockwise to reduce the pressure; coun-
terclockwise to increase. At the end tighten the locking nut.
The minimum current necessary to operate the control-box is 3
µA (Landis LGB22). When the measurement of the current is
required it is necessary to disconnect the lead to the probe and
insert in its place a microammeter for direct current (see fig.
under).
SETTING THE FIRING HEAD
A
--
+

POSITION OF ELECTRODES

Ignition electrode
IONIZATION CURRENT
pag.12
REMOVING THE BLAST TUBE
+
1
4
0
+
1
1
4
0
1
6
M
I
L
C
A
B
min. 3 μA
1
LANDIS LGB 22
Microamperometro
fondo scala 50 μA
N
D
H
G
E
F

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Blu 1700.1 pabBlu 2000.1-20 pabBlu 2000.1 pab

Table des Matières