5.8 Alarm management

In an alarm/warning situation, follow the procedure below:
set
Press
to enter menu of direct parameters.
to fi nd parameter " AL " .
Use the arrows
or
set
Press
to see alarm code:
set
AL
HiSt
esc
.....
Hd
Alarm list
Cod.
Description
Ld
Low dew point
Lt
Low evaporation temperature
Ht2
High discharge temperature
HP
High pressure
LP
Low Pressure
PI
Compressor Thermal protection
PH
Inverted phases
Warning list
Cod.
Description
FB0
B0 sensor warning
FB2
B2 sensor warning
FB8
B8 sensor warning
FB5
B5 sensor warning
FPI
PI sensor warning
DrE
Condensate drain warning
Hd
High dew point warning
Ht1
High discharge temperature
HB5
High evaporator temperature
English

5.9 Alarm history

To see current or previous alarms, follow the procedure below:
set
to enter menu " HiSt " .
Press
set
Press
to enter parameters :
Menu
Code
HiSF
HiSP
HySC
HiSt
HySd
set
HySt
Reset
M
esc
M
M
M
M
HiSt
M
M
Reset
A
A
A
A
A
A
A
A
A
Description
General alarm number
Alarm position
Alarm code
Alarm date
(if clock option is present)
Alarm hour
(if clock option is present)
set
HiSt
set
HiSP
HiSF
HiSC
HiSd
PSE 325-1000 60Hz
5.10 Setting clock/date.
1. Press "
" "
", together at the same time to enter menu
"FrEE".
set
2. Press "
" to enter menu "Ai".
3. Press "
" to enter menu "CL".
set
4. Press "
" to enter and view parameter "HOUr".
set
5. Press "
" until the screen fl ashes "HOUr".
6. Select the fl ashing parameter "HOUr"/"dAtE"/"4EAr" using the
set
button "
" and press "
" to enter.
7. Change the fl ashing value using "
"and "
set
and press "
" to confi rm.
esc
8. Press "
" to return to the menu "FrEE".
9. Press "
" "
" together at the same time to exit.
Fig.3
set
dr4
FrEE
Ai
FrEE
esc
4EAr
dAtE
set
set
18.20
2015
01.09
set
!
If the controller is left without power for more than three days,
the time and date will be reset. The time and date will have to be
reset during next start-up.
" (up and down)
CL
set
HOUr
set
5 sec.
HOUr
set
17.15