Air Flow Verification - Granby 100 Serie Instructions D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

The blower will start at the highest speed. 
When the cooling demand is satisfied: 
The blower will keep running on low speed. 
 
NOTES: 
The power switch has no effect on cooling mode when there is a cooling demand from the thermostat. 
If  a  two  stage  thermostat  is  used,  remove  the  jumpers  between  W1  &  W2.  If  a  three  stage  thermostat  is 
used  remove  the  jumpers  between  W1  &  W2  and  between  W2  &  W3.  In  this  mode  the  thermostat  will 
automatically control the sequence between the different elements and the motor speeds. In such a case, it 
is imperative that the power switch be at its maximum position (center position), i.e. 15KW for model 215, 
18KW for model 218 and 19KW for model 219. 
In  the  above  examples,  the  operation  is  similar  for  models  218,  219,  318  and  319.  The  three  settings  are, 
respectively, 9KW with low speed, 13KW with medium speed and 18KW with medium speed for model 218 
and 319 and 9KW with low speed, 14KW with medium speed and 19KW with medium speed for model 219 
and 319. 
REMEMBER TO VERIFY THE POWER SWITCH POSITION WHEN TROUBLESHOOTING PROBLEMS THAT RELATE 
TO  THE  FURNACE  NOT  SUPPLYING  ENOUGH  HEAT  OR  WHEN  MEASURING  A  CURRENT  LOWER  THAN 
EXPECTED.  
 
6.0 Air flow verification 
After the installation, it is CRITICAL that proper air flow be verified. This is done by taking the difference of temperatures 
(delta  T)  between  the  inlet  plenum  and  the  supply  (warm  air)  plenum.  Take  4  or  5  measurements  in  the  duct  and 
calculate  the  average  for  the  warm  air  duct.  This  temperature  differential  must  be  in  accordance  with  the  table  in 
section  1.3.  If  the  temperature  difference  is  much  higher  than  table  1,  2  or  3  of  section  1.3  for  the  specified  power 
setting, it is an indication that restriction in the heating system is much larger than normal. This might be caused by an 
obstruction or a clogged air filter. It is also possible that your house has an abnormally high pressure restriction. In that 
case it is possible to use the high speed of the blower. To do this, internal connections to the motor must be transferred 
from  the  medium  speed  tap  to  the  high  speed  tap  on  the  motor.  Refer  to  the  electrical  diagram.  It  is  strongly 
recommended that this modification be done by a qualified technician or electrician. Note the Delta T's in the table 
below. This information will be very valuable when doing annual maintenance. Please note that the factory settings for 
the blower are: 
Series 100 
o 15KW, 18KW and 19KW without cooling coil (0.20" W.C.): medium speed. 
o 15KW, 18KW and 19KW with cooling coil (0.50" W.C.): high speed. 
Series 200 and 300 
o 5 KW and 10KW power setting on Econoplus‐215 and 315: low speed. 
o 9 KW power setting on Econoplus‐218, 219, 318 and 319: low speed. 
o 13 KW power setting on Econoplus‐218 and 318: medium speed. 
o 14 KW power setting on Econoplus‐219 and 319: medium speed. 
o 15 KW power setting on Econoplus‐215 and 315: medium speed. 
o 18 KW power setting on Econoplus‐218 and 318: medium speed. 
o 19 KW power setting on Econoplus‐219 and 319: medium speed. 
o All models with cooling coil (0.5" W.C.): high speed. 
 
 
 