Granby 100 Serie Instructions D'installation page 22

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Also note that the blower in the rear compartment can be removed by loosening the 4 wing nuts (figure 3) that hold it to 
the  blower  supports.  The  wire  is  long  enough  so  you  can  remove  the  blower  from  the  unit  without  disconnecting  it. 
CAUTION: when removing the blower, DO NOT remove the blower legs. Loosen the 4 wing nuts and  slide the blower 
out.  To  replace  the  blower,  position  the  studs  in  the  slots  on  the  blower  legs  and  fully  insert  the  blower.  Be  sure  to 
RETIGHTEN the wings nuts after reinstalling the blower. Consult figure 4 for details. 
 
 
 
 
 
 
 
 
Alternate filter rack position 
 
 
4.0 Electrical connection to the furnace 
4.1 240VAC – High voltage 
You  only  need  to  bring  a  2  conductors  wire  +  ground  to  the  furnace  for  the  series  100  and  200  and  a  3 
conductors wire + ground for the series 300. The only electrical "installation" to the furnace is this connection. 
All other wiring is factory installed/connected. Consult the local electrical codes for the size of the conductors 
needed between the distribution panel and the furnace and the grounding of the unit. The use of copper wires is 
recommended. If aluminum wire is used, make sure to respect all applicable codes.  
  
Alternate 240V 
Wiring connection 
 
4.2 24VAC – Low voltage (Thermostat and controls) 
All 24VAC connections are done on the left portion of the upper front panel on the 8 positions magnum style 
terminal (recessed and accessible by removing the 2 screws on the small access panel). The terminology used is 
the standard HVAC terminology. Please refer to figure 6. 
 
Figure 3
Figure 4
Rotation of 
Supply block 
Factory designed
240V connection 
Wing Nuts
Also  note  that  it  is  possible  to  change  the 
orientation  of  the  main  terminal  block  in  the 
furnace  to  accommodate  a  supply  wire  coming 
from the left or right. The factory installed position 
is on the right side. Knock‐outs are provided on the 
left and right side panels.  If you choose to reorient 
the main supply block, you will have to disconnect 
and  reconnect  the  internal  wires  to  the  block.  To 
do  this,  consult  the  electrical  diagrams  in  the 
following  pages.  THIS  CAN  ONLY  BE  DONE  BY  A 
QUALIFIED  TECHNICIAN  AND/OR  ELECTRICIAN. 
Fig.5  above  shows  the  different  possible 
configurations. 
 
 

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

200 serie300 serie115118119215 ... Afficher tout

Table des Matières