4.2
Positioning on a slope, embankment etc.
If the grease separator is installed in the
immediate proximity (< 5 m) of a slope,
mound or embankment (greater than 5°), a
statically calculated supporting wall must be
constructed to bear the pressure of the soil.
The wall must exceed the tank dimensions
by at least 500 mm in all directions and must
be at least 1000 mm away from the tank.
4.3
Installation next to driven-on surfaces
If the grease separator is installed next to
roadways, the minimum distance from these
surfaces must be at least the depth of the
ditch (H).
mail@graf.info
www.graf.info
4. Installation and assembly
14 / 32
> H
H