DO: TM31
HEM - Status word 1
Bit no.
Meaning
0
1 = Operation
1
1 = Immediate stop active
2
1 = Ready for switching on
3
0 = Alarm active
4
0 = Fault active
5
1 = Run-on time active
6
1 = Pump 1 actuated
7
1 = Pump 2 actuated
8
1 = Increase temperature setpoint to prevent condensation active
9
1 = Automatic operation for condensation prevention active
10
1 = Control valve setpoint specification active
11
1 = MANUAL operation active
12
1 = Raw water circuit flow outside tolerance
13
1 = Leakage detected