Troubleshooting - Toshiba RAV-GP801AT-E Mode D'emploi

Masquer les pouces Voir aussi pour RAV-GP801AT-E:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 11
How to check the existing piping settings
You can check whether the existing piping settings are enabled.
1.
Check that the LED displays are placed in their initial status. If not, place them in the initial status.
2.
Hold down SW01 for at least 5 seconds, and check that D804 flashes slowly. (Fig. 9)
3.
Press SW01 four times to set the LED displays (D800 to D805) to the "LED displays for existing piping settings"
shown below. If the setting is enabled, D802 lights and D804 and D805 flash rapidly. (Fig. 10)
4.
Hold down SW01 and SW02 simultaneously for at least 5 seconds to return the LED displays to the initial status.
(Fig. 9)
LED displays indicated when step 3 is taken
D800
D801
D802
D803
D804
:ON,
:OFF,
:Slow flashing
When restoring the factory defaults
To restore the factory defaults in situations such as when relocating the units, follow the steps below.
1.
Check that the LED displays are placed in their initial status. If not, place them in the initial status.
2.
Hold down SW01 for at least 5 seconds, and check that D804 flashes slowly. (Fig. 11)
3.
Press SW01 20 times to set the LED displays (D800 to D805) to the "LED displays restored to factory defaults"
shown below. (Fig. 12)
(Fig. 11)
LED displays indicated when step 2 is taken
D800
D801
D802
D803
D804
:ON,
:OFF,
:Slow flashing
4.
Hold down SW02 for at least 5 seconds, and check that D804 flashes slowly. (Fig. 13)
5.
Hold down SW01 and SW02 simultaneously for at least 5 seconds to return the LED displays to the initial status.
(Fig. 13)
LED displays indicated when step 4 is taken
D800
D801
D802
D803
D804
:ON,
:OFF,
:Slow flashing
EN-177
(Fig. 10)
LED displays for existing piping settings
D805
D800
D801
D802
D803
:ON,
:OFF,
:Rapid flashing
(Fig. 12)
LED displays restored to factory defaults
D805
D800
D801
D802
D803
:ON,
:OFF,
:Rapid flashing
D805
14

TROUBLESHOOTING

You can perform fault diagnosis of the outdoor unit with the LEDs on the P.C. board of the outdoor unit in addition to
using the check codes displayed on the wired remote controller of the indoor unit.
Use the LEDs and check codes for various checks. Details of the check codes displayed on the wired remote
controller of the indoor unit are described in the Installation Manual of the indoor unit.
LED Displays and Check Codes
D804
D805
No.
Trouble description
1
Normal
2
Discharge temp. sensor (TD) trouble
Heat exchanger temp. sensor (TE)
3
trouble
Heat exchanger temp. sensor (TL)
4
trouble
Outside air temp. sensor (TO)
5
trouble
6
Suction temp. sensor (TS) trouble
7
Heat sink temp. sensor (TH) trouble
D804
D805
8
Miss-mounting of sensor (TE, TS)
9
EEPROM trouble
10 Compressor break down
11 Compressor lock
12 Current detection circuit trouble
13 Case thermostat operation
14 Unset model type of P.C.board
15 MCU communication trouble
16 Discharge temp. trouble
17 High pressure SW operation
18 Power supply trouble
19 Heat sink overheat trouble
20 Gas leak detection
21 4-way valve inverse trouble
22 High pressure protective operation
23 Fan system trouble
Short-circuit of compressor drive
24
element
25 Position detection circuit trouble
- 89 -
···ON
···OFF
···Rapid flashing (5 times/sec)
LED display
D800 D801 D802 D803 D804 D805
<GP110, GP140>
SW01
SW02
LED
(D800 to D805)
<GP80>
SW01
SW02
LED
(D800 to D805)
EN-178

Publicité

Table des Matières
loading

Table des Matières