Wiring between Indoor Unit and Outdoor Unit
The dashed lines show on-site wiring.
Input power
Circuit breaker
• Connect the indoor/outdoor connecting wires to the identical terminal numbers on the terminal block of each unit.
Incorrect connection may cause a failure.
For the air conditioner, connect a power wire with the following specifications.
Power and Wiring Specifications
Model (RAV- Type)
Power supply
Maximum running current
Recommended field fuse
Power wire*
Outdoor earth wire
Indoor/outdoor connecting wire*
(with earth wire)
×
* Number of wire
wire size
EN-169
Outdoor unit
Indoor unit
Wired remote controller
L
1
1
N
2
2
Α
Β
3
3
GP80
GP110
1 to 50 Hz 220 - 240 V
20.8 A
22.8 A
25 A
×
2
2
2.5 mm
or more
(H07 RN-F or 60245 IEC 66)
×
2
1
2.5 mm
or more
×
2
4
1.5 mm
or more
(H07 RN-F or 60245 IEC 66)
How to wire
1.
Connect the connecting wire to the terminal as
identified with their respective numbers on the
terminal block of the indoor and outdoor units.
H07 RN-F or 60245 IEC 66 (1.5 mm
2.
When connecting the connecting wire to the outdoor
unit terminal, prevent water from coming into the
outdoor unit.
3.
Secure the power supply wire and indoor/outdoor
connecting wires using the cord clamp of the
outdoor unit.
4.
For interconnecting wires, do not use a wire joined
to another on the way.
Use wires long enough to cover the entire length.
5.
Wiring connections differ in conformance to
EMC standards, depending whether the system
is twin. Connect wires according to respective
instructions.
CAUTION
GP140
• Fuse must be used in installation for the power supply
line of this air conditioner.
22.8 A
• Incorrect/incomplete wiring may lead to an electrical
fire or smoke.
• Prepare an exclusive power supply for the air
conditioner.
• This product can be connected to the mains power.
Fixed wire connections:
A switch that disconnects all poles and has a contact
separation of at least 3 mm must be incorporated in
the fixed wiring.
- 85 -
Wiring diagram
* For details on the remote controller wiring/installation,
refer to the Installation Manual enclosed with the
remote controller.
2
or more)
Single system
Remote controller
Remote controller wiring
Indoor side
Indoor/outdoor connecting
wires
Outdoor side
Simultaneous twin system
Remote controller
Remote controller
wiring
A B
Indoor side
1
2
3
Indoor/outdoor
connecting wires
1
2
3
Outdoor side
L
N
Power supply
A B
1
2
3
1
2
3
L
N
Power supply
Remote
controller
inter-unit
wiring
Indoor
A B
side
1
2
3
Indoor power
inter-unit
wiring
EN-170