KLSW 3 ⁄ KLSW 4
Series KLSW electronic airflow monitors are used for monitoring ventilators and dampers, for flow-dependent monitoring of humidifiers
and electric heating registers according to DIN 57100, part 420, or for applications in connection with DDC systems. Function: After
applying operating voltage (green LED lighting) and building up the desired flow velocity (yellow LED lighting) within the starting delay,
the »Alarm« relay is activated and the subsequent device is released. Sometimes detrimental heating ⁄ humidifying without air discharge
is so avoided. In case the necessary airspeed is not reached within the starting delay, the »Alarm« relay drops out.
Contacts 12 ⁄ 11 close. When preset flow rate is reached again, the »Alarm« relay is reactivated.
Contacts 11 ⁄ 14 close. By pressing the Reset button, the device is reset to its initial condition.
TECHNICAL DATA
Type
Item No.
Operating voltage
Voltage tolerance
Overvoltage category
Signal indication, voltage
Power consumption max.
Device ambient temperature
Signal output flow
Current ⁄ contact load
Switching function at flow
Signal indication at flow
Start bridging
Start bridging indication
Media temperature range
Temperature gradient
Switchpoint
Measuring range
Response time
Measuring sensor
Immersion depth
Process connection
Sensor material
Pressure resistance
Connection
Protection type, housing
Protection type, sensor
Contamination class
Housing dimensions
Test mark
Accessories (included)
Start bridging
Jumper plugged
Jumper not plugged
KLSW 4
24V AC ⁄ DC
± 10%
II
green LED
2 VA
–20..+60 °C
1 changeover contact
250 V AC, 6 A, 1.5 kVA
relay activated
yellow LED
60 s (via jumper)
yellow LED
–10..+80 °C
15 K ⁄ min
adjustable via potentiometer
0.1 - 30 m ⁄ s
1...10 s
built-in
130 mm
PG7, mounting flange
MS 58, nickel -plated
10 bar
5 terminals, 2.5 mm
IP 65
IP 67
2
108 x 70 x 73.5 mm (Thor II)
0
mounting flange 10 mm
= start bridging active for ca. 60 s, yellow LED »Time« lighting
= start bridging inactive
adjustable via potentiometer
2
108 x 70 x 73.5 mm (Thor II)
14
KLSW 3
230 V ⁄ AC
± 10%
II
green LED
4 VA
–20..+60 °C
1 changeover contact
250 V AC, 6 A, 1.5 kVA
relay activated
yellow LED
60 s (via jumper)
yellow LED
–10..+80 °C
15 K ⁄ min
0.1 - 30 m ⁄ s
1...10 s
built-in
130 mm
PG7, mounting flange
MS 58, nickel -plated
10 bar
2
5 terminals, 2.5 mm
IP 65
IP 67
2
0
mounting flange 10 mm