2.4

Electric hooking

Check features of electric supply, that have to comply with rating plate data.
With three-phase pump, verify rotation that has to be clockwise; operator checks rotation looking at cooling fan.
Motor pump is equiped with automatic reset thermal protector that cut off +266°F.
2.5

General precautions

Motor pump always must be suitably grounded.
Even if pump temperature never rise to high level during evacuation, be sure to locate pump so never results
damages as small burns.
When pump is a part of an eqipment, fixing must be such as to be safe for operator.
Motor pump is air cooled with fan; operate in open air with fan guard far away from walls or obstacles no less than 2".

3. Pump use

To grant reliability and high quality level, each pump is subjected in factory to a rigorous testing and suitable
preliminary running in.
Constant performances and long operative life are assured by strict observance of following procedure:
3.1

Pump start

Before first run, it is mandatory:
- fill the pump with oil (see section "2.1 Oil filling")
- let the pum running for few minutes with closed suction connection.
Check oil level on the occasion of following starting.
In case of malfunctioning, stop the pump and call Assistance Service.
3.2

Pump stop

Be sure to shut off suction piping before to stop the pump; this to prevent atmospheric air, present at exaust port,
from pushing oil into evacuated circuit when pump stops.
Mixture of incompatible lubricants (pump oil and compressor oil) causes malfunctioning to the pump.
In case of frequent on-off cycling, don't stop the pump but shut off suction flexible hose so, it's possible disconnect
it from evacuated circuit leaving the pump runs.
Before stop, let the pump run few minutes with gas ballast valve open and suction close; that to eliminate humidity
and residual refrigerant into the pump oil.

4. Routine maintenance

Periodic and correct maintenance of high vacuum pump allows long operative life and constant stated performances.
4.1

Lubrication

Oil provided with the pump has been expecially manufactured to lubricate high vacuum pumps; minimum viscosity
fluctiation in a range of temperature from +50°F up to +212 °F, marks it out.
Its chemical features allow to evacuate circuit operating with CFC or HCFC refrigerants (R12, R22, R502 etc.);
manufacturer suggests to fill in the pump with syntetic oil to evacuate circuits operating with HFC refrigerants
(R134a, R404a etc.); syntetic oil is available upon request.
Charges to fill in pumps are specified in section "1.1 General performance and technical data".
Replace first oil charge no later than 150÷200 hours running; take following replacement any 400÷500 hours
running or every 3÷4 months.
Lubricants - available models for routine maintenance
Mineral oil
Model: K1-L
Code: 10200027
Viscosity: ISO68
Packaging: 2.2 lb
4.2

Oil changing

Over-used lubricant damages the pump mechanism; take care to change oil as soon as it starts clouding.
Operate oil changing with pump not running.
For oil changing proceed as follows:
a)
unscrew oil drain plug located in lower part of the pump
b)
check used oil come out the pump
c)
tightly screw on oil drain plug
d)
fill the pump with oil (see section "2.1 Oil filling")
Don't pollute environment wasting oil; lubricant is a special waste and must be disposed according
to law in force.
14
Syntetic POE oil
Model: SW68
Code: 10200028
Viscosity: ISO68
Packaging: 2.2 lb
WARNING
User and service manual