Power Wiring Diagram - Carrier 80HMA Mode D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 75
Installation

Power wiring diagram

Refer to pic. 11 for the power diagram connection and to
the Safety Information Manual.
1. Comfort Module electric heaters power supply and
breaker (connected to pins L/L1,L2,L3 and N in the
Comfort Module connector).
2. Main boards power supply and braker (connected on
Pins 1 and 2 in the Comfort Module connector).
Comfort Module
Power supply
Operating voltage limits
Board and auxiliary devices power
consumption (max)
Boards and auxiliary circuit breaker
protection (not included) (Reference 2
in pic. 11)
Electric heater power consumption
Electric heater circuit breaker protection
(not included) (Reference 1 in pic. 11)
Running current (max)
Main power cable size
Communication cable
User interface (additional or remote)
cable
Booster heater power supply cable
Booster heater activation cable
Sanitary hot water sensor cable
Remote outdoor sensor cable
Voltage
V
Frequency
Hz
Phases
#
V
kW
kW
A
mm²
FROH2R
FROH2R
H05VV-F
FROH2R
FROH2R
FROH2R
3. Heat pump power supply and brakers. Follow the heat
pump installation manual instruction.
4. Sanitary water tank electric heater power supply and
breaker (dimension the breaker and cables according to
electric heater power and local law).
5. Main power supply source and breakers (Install
breakers according to the maximum power
consumption, according to the local law).
80HMA
M00
M03
M06
230
1
207-253
1.15
1.15
1.15
C6
C6
0
3
C6
C20
C32
5
18
3G x 2,5
3G x 4
3G x 6
mm²
mm²
mm²
2 x 0,75 mm²
4 x 0.75 mm²
3G x 2.5 mm²
2 x 1 mm²
2 x 0.5 mm²
2 x 0.5 mm²
T06
T09
400
50
3
360 - 400
1.15
1.15
C6
C6
C6
6
6
9
C16
C20
31
14
18
5G x 2,5
5G x 4
mm²
mm²
80HMA
7

Publicité

Table des Matières
loading

Table des Matières