350-20063
Read the complete manual before carrying out the installation and activating the system. keep the
manual for future reference.
1. DESCRIPTION
The 360° presence detector (1 – 10 V) consists of an integral unit with control of one 1 – 10 V output, a motion
sensor (PIR or passive infrared technology), a light sensor and an integrated IR receiver. All external units, such as
push buttons and lighting fixtures, are directly connected to the presence detector, which is mounted directly on
the ceiling.
The presence detector can be installed and operated on the basis of the factory settings. For optimal lighting
control, it is recommended to adjust the factory settings to the environmental conditions and to the specific lighting
requirements. The settings can be adjusted using the IR remote control (not included) (350-20064).
2. INSTALLATION
2.1. Connection
Danger: Disconnect all power before installing the presence detector. Do not connect the device to the mains
voltage until installation has been completed.
Refer to the wiring diagram (fig. 1) and the basic circuit diagram (fig. 2).
2.2. Mounting
Tip: Do not install the presence detector in direct sunlight or in the vicinity of heat sources (radiators) or air
currents (ventilation or air conditioning) (fig. 3). This can activate the sensor unnecessarily.
1. a. For direct mounting on the ceiling (fig. 4A), use the holes with a centre distance of 105 mm. The
cable inlet must be rotated 45° with respect to the mounting holes.
b. For mounting in a flush-mounting box (fig. 4B), use the holes provided with a centre distance
of 60 mm, with which you push open the protection cap. Carefully install the cable following the
instructions for a permanent installation.
2. Push the sensor onto the terminal strip on the base and tighten the screw (fig. 5).
3. Set the presence detector (fig. 6) and test the device (see sections 4.1. and 4.2.).
4. Reduce the detection area, if necessary (fig. 7).
5. Install the protection cap (fig. 5).
3. SETTINGS
3.1. Factory settings
At delivery the parameters of the presence detector are set as follows:
Parameter
application
light sensitivity
hysteresis on light sensitivity
light level of the orientation lighting
switch-off delay
switch-off delay of the orientation lighting
lux value and switch-off delay setting
3.2. DIP switches
Figure 6 shows how to set the DIP switches according to their application.
DIP switch
1
2
3 and 4
3.3. Indication LEDs
Mode of operation
The red indication LED is flashing.
The green indication LED is flashing.
The blue indication LED is illuminated.
The blue indication LED is flashing.
10
EN
nv Niko sa
Factory setting
manual
300 lux
20%
5%
10 min
1 min
via IR remote control
Application
You select this to set the lux value (LUX) and the
switch-off delay (TIME) via the potentiometers or the
IR remote control.
Not applicable.
You set the sensitivity of the motion sensor:
minimum, low, high or maximum.
Meaning
The presence detector detects presence in test
mode.
The push button or the IR remote control is
activated. When you press a button on the IR remote
control while the sensor is not locked, and the green
indication LED is not flashing, it means the sensor
has already reached its minimum or maximum
settings.
The test mode has been selected.
While you are setting the light sensitivity, this
indicates overlighting.
Industriepark West 40, BE-9100 Sint-Niklaas, Belgium — tel. +32 3 778 90 00 — fax +32 3 777 71 20 — e-mail: support@niko.be — www.niko.eu
4. IR REMOTE CONTROL
With the IR remote control (fig. 8), you can switch on or off and dim the lighting, select another application,
perform a test or enter other parameters.
4.1. Function buttons
Button
4.2. 'Set' buttons
Button
Function
You switch the lighting on.
The lighting remains switched on as long as there is
activity and the switch-off delay is activated.
You switch the lighting off.
The lighting remains switched off as long as there is
activity and the switch-off delay is activated.
Press this button to brighten the lighting. If you
press this button again, dimming will stop.
The lighting remains switched on as long as there is
activity and the switch-off delay is activated.
Press this button to dim the lighting. If you press
this button again, dimming will stop.
The lighting remains switched off as long as there is
activity and the switch-off delay is activated.
You switch over to daylight-dependent lighting.
The lighting remains switched on as long as there
is activity and the switch-off delay and orientation
lighting delay are activated.
The detection area is tested by activating the
integrated motion sensor for the walking test:
- The lighting is switched on for five seconds and
the red indication LED is flashing each time the
sensor detects activity.
- The blue indication LED is illuminated as long as
the sensor is in the test mode.
- After five minutes, the device automatically returns
to the control mode if you forget to close the test
mode.
The light sensor does not work during the walking
test.
symbol to select the automatic
- Press
application. You deactivate the manual
application.
- Press
to select the manual application. You
deactivate the automatic application.
After you made your selection, the sensor begins
with a soft start for correct initialisation.
You switch the indication LED on or off.
Function
- You use the red buttons only during start-up to set
the reference points.
- With these red buttons, you set the desired light
level (50 – 1500 lux) at table height.
- Each time you press the button, the light level
increases or decreases.
- When setting, the lighting is switched on for
demonstrating the light level chosen.
- With these blue buttons, you set the switch-off
delay (1 – 60 min).
- Each time you press the button, the switch-off delay
increases or decreases by 1 minute or 10 minutes.
- With these blue buttons, you set the switch-off
delay (1 – 60 min) for the orientation lighting.
- Each time you press the button, the switch-off
delay increases or decreases by 1 minute or
10 minutes.
- With these buttons, you set the positive hysteresis
on light sensitivity (10 – 100%) for the light
level.
- Each time you press the button, the hysteresis
increases or decreases by 10%.
- With these buttons, you set the light level of the
orientation lighting (5 – 100%).
- Each time you press the button, the light level
increases or decreases by 5%.
- The device returns to the factory settings.
- The sensor begins with a soft start for correct
initialisation.