S+S Regeltechnik AERASGARD ACO2 Notice D'instruction page 15

Sonde transmetteur de gaine/en saillie multifonctionnelle, pour i'humidite, la temperature, la teneur en co2 et la qualite de fair cov, etalonnable, avec raccordement modbus
Masquer les pouces Voir aussi pour AERASGARD ACO2:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

G
®
HYGRASGARD
Display
standard
By default, the display indicates the following measurements with the
corresponding units cyclically and consecutively:
CO2 content in ppm, air quality (VOC) in %,
temperature in °C, relative humidity in % r.H.
Backlighting is provided for improved legibility.
The Modbus interface allows the display to be individually configured,
both in the 7 segment range and in the dot-matrix range.
Display - individually
programmable
Automatic calibration of the carbon dioxide measurement – (default)
Automatic zero point calibration is deactivated by default in the as-deli-
vered condition and, if required, must be activated using the Modbus.
Schematic diagram
Plug for
display
B
4
A
3
GND
2
1
U+
shield
AFTM- ⁄ KFTM - LQ - CO2 - Modbus
mode
ON
1 2 3 4 5 6
CO ² VOC
zero
DIP A: Bus address
DIP B: Bus parameters
Display
alternative output variables
The Modbus interface can be used to program an alternative output
variable instead of the standard display.
In this case, the first line indicates the value while the second line
indicates the corresponding unit statically.
The index in the third line indicates the display type:
Index 1 = CO2 content in ppm
Index 2 = air quality (VOC) in %
Index 3 = temperature in °C
Index 4 = relative humidity in % r.H.
Index 5 = atmospheric pressure in hPa
Plug for
display
Zero point calibration
The sensors are pre-set and calibrated at the factory.
Each measuring channel has a separate offset potentiometer
for subsequent adjustment of the measurement.
B
4
The adjusting range is ± 10 % of the measuring range.
A
3
GND
2
1
U+
shield
offset
CO ²
VOC
r.H.
°C
address
DIP B
DIP A
ON
1 2 3 4 5 6 7 8
B
4
A
3
GND
2
U+
1
shield
15
CO ²
mode
ON
DIP B
ON
1 2 3 4 5 6
1 2 3 4 5 6 7 8
CO ² VOC
zero
DIP A: Bus address
DIP B: Bus parameters
(Baud rate, parity ...)
Telegram indicator
Reception (LED green)
Error (LED red)
Offset correction
LED (internal status)
Reset button
Rev. 2021 - V25
offset
VOC
r.H.
°C
address
DIP A
B
4
A
3
GND
2
U+
1
shield

Publicité

Table des Matières
loading