Parameter
COOLING CLIMATE
CURVE FOR MAXIMUM
WATER TEMPERATURE
OUTSIDE AIR COOLING
CLIMATE CURVE FOR
MAXIMUM WATER
TEMPERATURE
OUTSIDE AIR COOLING
CLIMATE CURVE FOR
MINIMUM WATER
TEMPERATURE
COOLING CLIMATE
CURVE FOR MINIMUM
WATER TEMPERATURE
OUTSIDE AIR HEATING
CLIMATE CURVE FOR
MAXIMUM WATER
TEMPERATURE
HEATING CLIMATE
CURVE FOR MAXIMUM
WATER TEMPERATURE
OUTSIDE AIR HEATING
CLIMATE CURVE FOR
MINIMUM WATER
TEMPERATURE
HEATING CLIMATE
CURVE FOR MINIMUM
WATER TEMPERATURE
SERVICE MENU
PASSWORD
PERIPHERAL ADDRESS
56
DISPLAY
MENU
MNEMONIC
Cc1
Service
Cc2
Service
Cc3
Service
Cc4
Service
Hc1
Service
Hc2
Service
Hc3
Service
Hc4
Service
PAS
Service
rtF
Service
Adr
Service
Range of
Factory
setting
-15 – +50°C
20°C
18°C
4°C -20°C,
7°C -27°C
-15 – +50°C
40°C
15°C
4°C -20°C,
7°C -27°C
-15 – +50°C
-5°C
35°C
20-60°C,
20-55°C
-15 – +50°C
20°C
28°C
20-60°C,
20-55°C
0 – 200
0
1 – 255
1
COMMENTS
Factory settings for
fan coils and control of
systems with leaving
water temperature
Factory settings for
fan coils and control of
systems with leaving
water temperature
Value held by Olimpia
Splendid Service
RS485 communication
port address to be used
with any remote control