REMOTE CONTROL
Some appliance functions can be controlled remotely using free contacts.
terminal 1:
terminal 2:
terminal 3:
terminal 4:
terminal 5
terminal 6:
CIRCULATION PUMP CHECKS
The circulation pump can run in different modes depending on the requirements of the system to which the unit is connected:
parameter Pqd sets every how many hours the start-up is set for and parameter Pqt sets how long the pump is to run
during the anti-locking cycle.
DOMESTIC WATER PRODUCTION
The appliance can be connected to a tank with an intermediate exchanger to produce domestic water. The 3W internal units
The domestic water request can occur in two ways:
below 60°C.
set with parameter HS3.
Via parameter hyS it is also possible to check the hysteresis cycle of the tank temperature check.
system and the system will continue to run in the same way as before the domestic water request.
towards the DHW tank. When the required temperature is reached, the compressor stops, the refrigerant cycle inversion
valve and the 3-way valve are switched and the compressor starts three minutes after the previous stoppage.
During domestic water production the system dispenses the maximum power possible to rapidly meet the domestic water
request.
ANTI-LEGIONELLA CYCLE
Through the activation of the anti-legionella function, the adjuster is able to conduct the thermal disinfection procedures
autonomously on domestic hot water systems, considerably reducing the risk of the presence and proliferation of the bacteria
responsible for legionella.
The disinfection function is activated in parameter Ldi. The user can opt to heat the domestic water with the heat pump and
The time interval for running the cycle in days, for how long and at what temperature to run the disinfection cycles are set
respectively in parameters LdS, Ldd and Ldt.
52
on/off: with the free contact open the system is in stand-by, with the contact closed the system is on
toggle heating/cooling operating mode: with the free contact open the system is in heating mode, with the
contact closed the system is in cooling mode
as per ECO mode set-point: with the free contact open the set-point selected is cS1 in cooling mode or HS1
night-time mode selection activation: with the free contact open the function is disabled, with the contact closed
the function is active
cooling or heating mode activation/inhibition. when the contact is open, the domestic water function remains
active. It may also be connected to a chrono-thermostat or in parallel to the chiller/boiler contacts of the electronic
controls of fan coils Bi2 and Bi2+.
The contacts must be closed on terminal L