Fitting and installation

Installation

Note!
Protection rating IP 30 must be achieved: Distribution boxes (Fig. 2) which
achieve a minimum protection rating of IP 30 must be used for the installation.
Attention!
Limitation of function with incorrect operating voltage at the components. A
mains adapter in accordance with DIN EN 60950–1 SELV must be used. Separate
mains adapters must be connected for the supply of devices with power con-
sumption higher than 100 VA. The appropriate mains adapter, the cable lengths,
and cable cross sections must be chosen according to the local circumstances.
Check and ensure that the operating voltage at the connection points is suitable
for the components.

Identification of the cable

Note!
Choose uniform identification for avoidance of errors: In order to avoid errors
and for a clearer overview during installation and maintenance, ASSA ABLOY Sicher-
heitstechnik recommends uniform identification and colour coding of the cable
cores Tab. 1.
Function
CAN_H
CAN_L
Hi-O
V
+
B
GND
Screw
terminal
Hi-O
1
wh
2
br
3
gn
4
ye
Colours
CAN bus
J-Y(ST)Y 4x2
wh/br
br
gn
wh/gn
Fitting and installation