FUEL KEROSENE
Nozzle
1
GPH
Angle
0.85
60°
1.00
60°
1.10
60°
1.25
60°
1.35
60°
1.50
60°
1.75
60°
2.00
60°
1.50
60°
1.75
60°
2.00
60°
2.25
60°
2.50
60°
3.00
60°
3.00
60°
For 2.50 - 3.00 GPH nozzles it is advisable to use, if possible full cones.
1
NOZZLES RECOMMENDED
PRESSURE
2
FOR LIGHT OIL INCREASE PRESSURE
8 bar:
the pump leaves the factory set at this value, which is suitable only for kerosene
10 bar: maximum pressure for kerosene.
12 bar:
pressure suitable for light oil in most cases
14 bar:
improves flame retention; it is therefore suitable for ignitions at low temperatures.
3
COMBUSTION HEAD SETTING
This is done when fitting the nozzle, with the blast
tube removed.
It depends on the output of the burner and is car-
ried out by rotating the regulating rod, till the termi-
nal plane of the blast tube is level with the set-
point, as indicated in the schedule.
In the sketch, the combustion head is set for an
output of 1.00 GPH at 12 bar (for gas-oil) or 1.25
GPH at 8 bar (for kerosene).
The shutter is level with set-point 3, as required
by the table at page 5.
Pump pressure
Burner output
2
bar
8
8.5
8
8
8
8
8
8
8
8
8
8
8
8
10
Monarch type R
Steinen
Danfoss type ES (only for kerosene)
7
Comb. head
adjustment
kg/h ± 4%
Set-point
2.5
3,0
3,3
3,7
4.0
4.4
5.2
5.8
4.43
5.17
5.91
6.64
7.38
8.86
9.99
Delavan type W - B
type Q
Danfoss type B - S
Terminal plane of the blast tube
D6106
Blast tube
GB
Air damper
adjustment
3
4
Set-point
1
1.2
0
2.6
2
1.8
3
2.2
3.5
2.4
4.5
2.7
6
3.2
6
4.2
1.5
2.6
2
2.9
2.5
3.3
3.5
3.5
4
3.8
5
5
6
6
2
5
3
1
Regulating rod
Shutter
2903360