Maintenance; General Conditions Of Sales And Delivery - oventrop NR 230 Instructions D'installation Et D'utilisation

Masquer les pouces Voir aussi pour NR 230:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Turn handle for manual setting to the left until stop.
Arrow of the handle is in the blue zone.
− Introduce screw together with the serrated lock
washer and tighten with a torque of >5Nm.
− Set operating switch to automatic operation.
"Nose"
2
red
blue
5
Illustr. 5.7 Installation 4-way mixing valve DN25 / DN32
5.5 Installation instructions for the connection to
a three-way mixing valve "Regumat M3"
DN40/50
Model 230V – 15Nm
− Mount antirotation device (1) onto the valve body as
illustrated.
− Push adapter (2) onto the spindle of the mixing valve
(3) until stop. Ensure flat surfaces on spindle and
adapter are aligned
− Set spindle of the mixing valve in such a way that
the long ridge of the adapter is at three o'clock
position. In this position, the right hand side
connection is closed by the spindle of the mixing
valve.
− Place actuator (3) onto the spindle of the mixing
valve with the adapter and antirotation device.
− Slip rotation indicator (5) onto the shaft of the mixing
valve with the arrow being in the red zone (left hand
limit stop).
− Introduce screw (4) together with the serrated lock
washer and tighten with a torque of >5Nm.
Installation in intermediate position:
Factory setting misaligned – actuator has not yet
reached limit stop.
− Mount antirotation device (1) onto the valve body as
illustrated.
− Push adapter (2) onto the spindle of the mixing valve
until stop. Ensure flat surfaces on spindle and
adapter are aligned
10
3
1
6
4
7
− Set spindle of the mixing valve in such a way that
the long ridge of the adapter is at three o'clock
position. In this position, the right hand side
connection is closed by the spindle of the mixing
valve.
− Set operating switch to manual operation.
− Place rotation indicator (5) onto the actuator (4) with
the red field pointing downwards.
− Slip handle for manual setting (7) onto the shaft of
the mixing valve.
Turn handle for manual setting anticlockwise until
stop. Arrow of the handle is in the red zone.
− Place actuator onto the shaft of the mixing valve.
− Introduce screw (4) together with the serrated lock
washer and tighten with a torque of >5Nm.
− Set operating switch to automatic operation.
1
2
red
6
5
4
3
Illustr. 5.8 Installation 3-way mixing valve DN40 / DN50

6 Maintenance

The actuator is maintenance-free.
7 General conditions of sales
and delivery
Oventrops general conditions of sales and delivery
valid at the time of supply are applicable.
long ridge

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Nr 24

Table des Matières