PREX H 3 COND
MODEL: PREX H 3 COND 150 (OIL)
Trademark: LAMBORGHINI CALORECLIMA
Condensing boiler: YES
Low-temperature boiler (**): NO
B1 Boiler: YES
Combination heater: NO
Cogeneration space heater: NO
Item
Rated heat output
Seasonal space heating energy efficiency
Useful heat out put
Useful heat output at rated heat output and high-temperature regime (*)
Useful heat output at 30% of rated heat output and low-temperature regime (**)
Useful efficiency
Useful efficiency at rated heat output and high-temperature regime (*)
Useful efficiency at 30% of rated heat output and low-temperature regime (**)
Auxiliary electricity consumption
At full load
At part load
In standby mode
Other items
Standby heat loss
Ignition burner power consumption
Annual energy consumption
Sound power level
Emissions of nitrogen oxides
(*) High-temperature regime means 60°C return temperature at heater inlet and 80°C feed temperature at heater outlet.
(**) Low temperature means for condensing boilers 30°C, for low-temperature boilers 37°C and for other heaters 50°C return temperature (at heater inlet).
MODEL: PREX H 3 COND 150 (GAS)
Trademark: LAMBORGHINI CALORECLIMA
Condensing boiler: YES
Low-temperature boiler (**): NO
B1 Boiler: YES
Combination heater: NO
Cogeneration space heater: NO
Item
Rated heat output
Seasonal space heating energy efficiency
Useful heat out put
Useful heat output at rated heat output and high-temperature regime (*)
Useful heat output at 30% of rated heat output and low-temperature regime (**)
Useful efficiency
Useful efficiency at rated heat output and high-temperature regime (*)
Useful efficiency at 30% of rated heat output and low-temperature regime (**)
Auxiliary electricity consumption
At full load
At part load
In standby mode
Other items
Standby heat loss
Ignition burner power consumption
Annual energy consumption
Sound power level
Emissions of nitrogen oxides
(*) High-temperature regime means 60°C return temperature at heater inlet and 80°C feed temperature at heater outlet.
(**) Low temperature means for condensing boilers 30°C, for low-temperature boilers 37°C and for other heaters 50°C return temperature (at heater inlet).
ErP product fiche
ErP product fiche
cod. 30902840 - Rev. 00 - 02/2018
Symbol
Unit
Value
137
Pn
kW
η
93
s
%
137,3
P4
kW
P1
kW
44,2
η
90,9
%
4
η
97,9
%
1
0,195
elmax
kW
0,170
elmin
kW
PSB
kW
0,003
0,990
Pstby
kW
Pign
kW
0,000
QHE
GJ
426
68
LWA
dB
NOx
mg/kWh
128
Symbol
Unit
Value
137
Pn
kW
η
s
%
92
137,3
P4
kW
45,4
P1
kW
η
87,4
%
4
η
96,8
%
1
0,230
elmax
kW
0,110
elmin
kW
PSB
kW
0,003
0,990
Pstby
kW
Pign
kW
0,000
QHE
GJ
432
66
LWA
dB
63
NOx
mg/kWh
EN