IMPORTANT
For installations of domestic hot water provide for a filter to protect the safety of
the systems. It is suggested to install a check valve and an expansion in AFS line.
In presence of water with hardness above 25 ÷ 30 ° Fr, is prescribed an appropriate
treatment of the heating water, in order to avoid limescale problems. It should
be noted that even a small quantity of limescale, could reduce the performances
of the domestic side.
The materials of construction are in compliance with the Directive 98/83 EC.
Despite the fittings are mounted at the factory, it is advisable to monitor all screw
connections. Equally important is to do a pressure test during the operation.
Exceeding above listed limits may cause damages to module and impair warranty
terms consequently
SECTION 3: DIMENSION AND CONNECTION
¾" F
1"M
65
65
65
70
185
¾" F
1"M
!
Assembling instrunctions and maintenance
DHW return
DHW outlet
Fig.1
M-F 1-¾"
DESCRIPTION
PH
Saturation factor(delta PH))
Total hardness
Conductivity
Sediments
Clorine
Hydrogen sulphide
Ammonia
Hydrogen carbonate
Hydrogen carbonate / sulphide
Sulphide
Nitrate
Nitrite
Sulphate
Manganese
Free iron
Free carbon dioxide
Primary supply
Fig.1
Primary return
DCW inlet
LIMIT VALUES FOR COPPER
UNIT
SOLDERED HEAT EXCHANGER
7-9 (including saturation factor)
-0.2<0<+0.2
°Fr
15-30
µS/cm
10...500
mg/l
<30
mg/l
<0.5
mg/l
<0.05
mg/l
<2
mg/l
<300
mg/l
>1.0
mg/l
<1
mg/l
<100
mg/l
<0.1
mg/l
<100
mg/l
<0.1
mg/l
<0.2
mg/l
<20