Lovato T-FAST ie40 Instructions Relatives À L'installation, L'utilisation Et La Maintenance page 19

Modules de production ecs
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

COMPONENTS
1
High efficiency pump type Wilo YONOS PARA 15/1-7
2
Black template frame
3
Black handle with red thermometer (primary circuit)
4
Ball valve DN25 with 1"½ nut and check valve
5
Brazed plate iron steel heat exchanger with insulation
6
10 bar safety valve secondary side (domestic water) F-F ½" - ¾"
7
Black handle with blue thermometer (primary circuit)
8
Ball valve DN20 M-F 1"- ¾" with nut
9
Red handle
10
Blue handle
11
Load / drain tap ½"
12
Robocal air vent G
/
"
1
4
13
MFWC digital controller
14
Vortex flow sensor 2-40 l/min
Accessories
16
Recirculation kit with high efficiency pump type Wilo YONOS PARA Z
15/7- PWM2 and PT1000 sensor.
TECHNICAL DATA
Primary circuit max. flow rate
DHW max. flow rate
DHW temperature set
Max. working pressure
Electricity supply - power consumption
Min. flow rate DHW/ON production
DHW PRODUCTION DATA
The proper working of the module is assured if the supply temperature of the primary circuit is at least 5°C greater than theD HW temperature set.
SECTION 2: TECHNICAL DATA
1.850 l/h
2.400 l/h ∆P 0,8 bar
40÷55 °C
6 bar
230 V AC, 48 W
2 ± 0,3 l/m
Assembling instrunctions and maintenance
9
4
9
7
2
Min. flow rate DHW/OFF intervention
Exchange surface
Dimensions with insulation (BxHxP):
Connections
Capacity
Weight
Buffer tank drawing temperature (°C)
2
1
10
5
6
6
3
3
2 ± 0,3 l/m
²
1,76 m
480x840x185 mm
¾" F - 1" M
6,6 l
19,2 Kg
19

Publicité

Table des Matières
loading

Table des Matières