Electrical Connection; Pnp Sensor; Nan Sensor - Ecolab OGM PVC 0,1 Notice Technique

Compteur à roues ovales
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5.7

Electrical connection

NOTE
ATTENTION
For sensors with no pre-installed connecting cable, connect the connector of the connect-
ing line onto the sensor and fix to the sensor using the union nut on the connector.
ATTENTION
Connect the other end of the connecting line (cable connecting sleeves) to a flow computer /
pulse counter (see Section 9, "Spare parts and accessories") in accordance with the following
circuit diagram in principle.
NOTE
5.7.1

PNP sensor

Fig. 5.7
5.7.2

NAN sensor

Fig. 5.8
417101446_Ovalradzaehler.doc
The oval gear meter on console (OGC) is equipped at the manufacturer's works with a PNP
inductive sensor ready for operation
Only a connecting cable and plug-type connector approved for connection of sensors may
be used for connection of the sensor
The plug-type connector can be connected to the sensor only in one position.
Never use force, since this could damage the sensor and/or the cable!
A load resistor must be installed between the "OUT" output and "GND" ground in case of
high-impedance outputs on the evaluator and in case of fast pulse sequences. A current of
not less of 2 mA should flow.
PNP NO
colour identification according to IEC757
BN
BK
BU
NPN NO
Colour identification according to IEC757
10...36V DC
BN
BK
OUT
BU
GND
10...36V DC
OUT
GND
- 27 -
Imax 200mA
Imax 200mA
Rev. 7-02.09