Friedrich M24CJ Manuel D'installation page 14

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

14
<Right side piping>
View
3
Tape the tubing pipe, drain hose and the
connection cable. Be sure that the drain
hose is located at the lowest side of the
bundle. Locating at the upper side can
cause overflow from the drain pan through
the inside of the unit.
<Left side piping>
NOTE
!
Insert the drain hose at left side when you
use left side piping type.
<Right side piping>
Connecting
cable
Drain hose
* The feature can be changed according to
the type of model.
CAUTION
!
Must use the elbow type
(L-Type) conduit
Method:
1. Disassemble bracket
(from indoor unit)
2. Assemble it with conduit
3. Reassemble it with indoor
unit.
CAUTION
!
If the extension drain hose is routed inside
the room, insulate the hose with an insula-
tion material* so that dripping from sweat-
ing (condensation) could not damage fur-
niture or floors.
• Foamed polyethylene or equivalent is
recommended.
Indoor
Outdoor
Indoor Unit
Drain hose
Tape
Connecting pipe
Insulation
(More than 100~300mm
Indoor Unit
Drain hose
length and 7mm thickness)
Extension
drain hose