Product and functional description,
Fan
If a water heating coil is used, the fan will start when heat is switched on. The fan con-
tinues to run for 30 seconds after the heat has been switched off. On condition, howev-
er, that the water heating coil is connected to the control signal through terminal points
1 and 2.
If the water heating coil is controlled externally and is not connected to the unit control,
the fan will not automatically be switched on when the water heating coil is connected.
The control of CDP 75/125/165 has an option for connecting an external ON/OFF
switch for continuous fan operation – allowing the fan to be running independently of
the dehumidification and/or heating requirements. The switch is connected to terminals
7 and 8 and the outlet for the switch is 12 V. The bridge between terminals 7 and 8 has
to be removed first.
Compressor
The number of compressor startings is limited by a 6 minutes timer, which starts up
when switching on the compressor. The timer must have come to an end before the
compressor can be switched on again.
The control system of the unit has a time delay of 30 seconds. This means that each
time the unit has been switched off on the main switch or on the hygrostat, it will take
30 seconds before the unit can be switched on again.
This is a safety function protecting the compressor against overloading caused by too
high pressure in the cooling circuit at the start-up.
LP/HP pressostat
The CDP 75, CDP 125 and CDP 165 are fitted with a reset button of the HP pressostat
on the inspection side
Thermal relay
The CDP 125(3x400V) and CDP 165(3x230V/3x400V) are additionally fitted with a reset
button for the thermal relays. This protects the compressor.
Klixon
The compressors in CDP 75(1x230V) and CDP 125(1x230V) are protected by a Klixon
and not by a thermal relay