AERASGARD
RCO2 - AS NT
Maintenance-free room sensor AERASGARD
in an elegant plastic housing, for determining the CO2 content of the air in the room (0...3000 ppm). The measuring transducer converts
the measurand to a standard signal, which is directly presented visually by five coloured LEDs (traffic light indicator). An additional acoustic
signal sounds when the next warning level is reached (can be switched off via DIP switch). Available in device version RCO2-AS NT ST with
metal stand for flexible positioning.
The room filter with CO2 traffic light is used in classrooms, training rooms and convention centres, offices, hotels, apartments, shops, etc.
and is used for easy and quick evaluation of the indoor climate. This enables energy-saving room ventilation on an as-needed basis,
thereby reducing operating costs and improving well-being. We recommend one sensor for every 30 m² of space.
The CO2 content is measured with an optical NDIR sensor (non-dispersive infra-red technology).

TECHNICAL DATA

Power supply:
Electrical connection:
Sensor:
Measurement range:
Measuring accuracy:
Temperature dependence:
Pressure dependence:
Long-term stability:
Gas exchange:
Ambient temperature:
Warm-up time:
Measuring interval:
Housing:
Dimensions:
Mounting:
Protection class:
IP rating:
Standards:
Equipment:
®
Mobile CO2 sensor for schools
AERASGARD
RCO2-AS NT
with traffic light display, acoustic signal and power supply unit
Type ⁄ WG02
Measuring ranges
CO2
RCO2-AS NT
RCO2-AS NT ST
0...3000 ppm
Note:
This unit must not be used as safety-relevant device!
®
RCO2-AS NT with traffic light indicator, acoustic signal and power supply, self-calibrating,
5 V DC (micro-USB) / 24 V DC
plug-in power supply unit, CL = approx. 1.5 m (included in the scope of delivery)
optical NDIR sensor (non-dispersive infrared technology),
with manual calibration (via zero button)
with automatic calibration
0...3000 ppm
typically ± 30 ppm ± 3 % of measured value
± 5 ppm ⁄ °C or ± 0.5 % of measured value ⁄ °C (whichever is greater)
± 0.13 % ⁄ mm Hg
< 2 % in 15 years
by diffusion
0...+ 50 °C
approx. 1 hour
< 3 seconds
plastic, material ABS, colour pure white (similar to RAL 9010)
85 x 85 x 27 mm (housing Baldur 1)
110 x 85 x 100 mm (housing and stand holder)
immediately usable free-standing device with wall power supply (plug-and-play)
III (according to EN 60 730)
IP 30 (according to EN 60 529)
CE-conformity, electromagnetic compatibility according to EN 61 326, EMC directive 2014 ⁄ 30 ⁄ EU,
low voltage directive 2014 ⁄ 35 ⁄ EU
traffic light display (five coloured LEDs, see table)
for indication of CO2 concentration
acoustic signal (see table)
when the next warning level is reached
plug-in power supply unit (connection cable approx. 1.5 m)
stainless steel stand
Display
CO2
5 LEDs,
signal tone
 Equipment
plug-in power supply unit,
stand holder
6
Rev. 0000 - V11
Item no.