Danfoss VLT MICRO Serie Mode D'emploi page 8

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 51
Wiring
There are two wiring systems in a frequency converter: Main circuit and Control circuit.
The Main Circuit terminals are located at the top of the drive. Control Circuit terminals
are located at the bottom of the drive, Both terminal blocks are covered by the plastic
housing. Lift the hinged portion of the housing to gain access to the terminals. Make
sure power is removed before making any connections. Connect wires to the terminals
according to the diagram below. When no connections are made to the control
terminals, the drive is operated by the Digital Keypad/Display.
200-240VAC
R
50/60HZ
(Select two
S
terminals as
input for single
T
phase models)
Ground
Factory set as
multi-function input terminals
Forward/Stop
Reverse/Stop
Reset
Multi-Step 1
Multi-Step 2
Multi-Step 3
Signal Common
Output Freq. determined
Analog voltage
0-10VDC
VR: 3K-5K ohm
Analog current
4-20mA
Factory set as, output frequency
determined by the potentiometer on
the control panel
Braking Resistor (Option)
Select 80 ohm 120V
/200 ohm 120V
B1
B2
R
U
S
V
T
W
E
F
M0
AFm
M1
M2
GND
M3
M4
RA
M5
RB
GND
RC
Power for
speed setting
MO1
+10V 10mA (max)
AV1
MCM
GND
6
VLT
®
MICRO
M
Grounding
Trim (1K ohm)
Analog
+
output
DC 0-10V
Factory set as,
Indication of output frequency
Multi-function indication output
contacts 120VAC/28VDC 5A
240VAC 2.5A
Factory set as,
Indication of fault
Multi-function PHC output
48V 50mA below
Factory set as,
Indication of Operation
Main Circuit (power) Terminals
Control Circuit Terminals

Publicité

Table des Matières
loading

Table des Matières