Lenze E84DGDVB 4 Serie Instructions De Montage page 99

Masquer les pouces Voir aussi pour E84DGDVB 4 Serie:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Keypad display
Par1 8400 motec
User menu
Load Lenze setting
C00002/1
9. Enable inverter: Set RFR to HIGH potential.
By default, the RFR terminal is bridged (controller enable).
If the auto−start option "Inhibit at power−on" is activated in C00142 and
the controller is enabled at mains connection, the controller remains in
the "ReadyToSwitchOn" status. For changing to the "SwitchedOn"
status, controller enable must first be deactivated. Only when the
controller is enabled again afterwards, the status changes to
"OperationEnabled":
If the autostart option "Inhibit at power−on" is deactivated in C00142,
the status directly changes from "ReadyToSwitchOn" to the
"SwitchedOn" state and to the "OperationEnabled" state after mains
connection when the controller is enabled.
}
Danger!
When the auto−start option "Inhibit at power−on" is deactivated, the
motor can directly start after power−on if the controller is enabled!
10. Select speed:
In the "Terminals 0" by selecting a voltage at the analog input or by
selecting a fixed setpoint via the digital inputs DI1/DI2.
In the "Keypad" control mode, the main speed setpoint and the control
signals are predefined via the following parameters:
EDK84DGDVBxxx4 DE/EN/FR/ES/IT 9−0
Commissioning via the diagnosis terminal
Action
A Select the menu in the main menu using the ƒ navigation key.
B Change to the menu using the … navigation key.
A Use the left function key ‰ to change to the editing mode for
C00002/1.
B Use navigation key ƒ to select the "1: On/Start" entry in the
selection list.
C Use the right function key ‹ to accept the executed change and quit
the editing mode.
– The load process may take a couple of seconds.
l
Commissioning
Commissioning steps
6
99

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

L-force 8400 motec

Table des Matières