Take care!! Before starting on any
maintenance work, the roof extract fan
must be disconnected from the mains
voltage.
Dismantle the mounting plates(6) by
unscrewing the bolts(5);
Remove the top cover of the roof
extract fan(7) and the protective grille(1);
Check that the impeller and the base
are not dirty;
When cleaning any components, take
care not to damage the protective layer.
Take care!! The roof extract fan must
not be sprayed with water or with a high
pressure cleaner.
Dismantle the power cable of the motor
from the connection box or switch;
Dismantle the roof extract fan cover(3)
by pulling the hood up and at the same
time pushing out the clamp springs(2);
Dismantle the mounting plate(9) by
unscrewing the bolts(8);
When cleaning the parts, make sure not
to damage the antistatic coating.
Take note! Do not place with the impeller
on the ground!
5
6
8
9
4
10
Dismantle the carrier plate of the
impeller(14) by unscrewing the bolts(15);
Take the impeller off the hub of the
motor;
Put everything back in the reverse
order.
Take note! The marking on the impeller
must be located facing the key way of
the motor shaft, as this is the position in
which the impeller is balanced.
Check: The anti-static coating must not
be damaged or come loose from the fan
housing;
Check whether the impeller moves
freely;
Turn on the fan briefly to check which
way the impeller turns;
Check the impeller to ensure it is
balanced;
Check the bearings of the motor.