Functional Check; Maintenance And Cleaning - WIKA LH-10 Mode D'emploi

Masquer les pouces Voir aussi pour LH-10:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

6. Commissioning, operation / 7. Maintenance and cleaning
Load in Ω
Current output (2-wire):
Current output (3-wire):
Voltage output (3-wire):

6.3 Functional check

The output signal must be proportional to the prevailing pressure. If this is not the case, this may indicate a damaged
diaphragm. In this case, see chapter 8 "Faults".

7. Maintenance and cleaning

7.1 Maintenance
This submersible pressure transmitter is maintenance-free.
Repairs must only be carried out by the manufacturer.
7.2 Cleaning
CAUTION!
Prior to cleaning, switch off and disconnect the submersible pressure transmitter from the voltage
supply.
Clean the instrument with a moist cloth.
Wash or clean the dismounted instrument before returning it, in order to protect persons and the environ-
ment from exposure to residual media.
Residual media in dismounted instruments can result in a risk to persons, the environment and
equipment. Take sufficient precautionary measures.
Do not use any pointed or hard objects for cleaning, as they may damage the diaphragm of the process
connection.
For information on returning the instrument see chapter 9.2 "Return".
WIKA operating instructions submersible pressure transmitter, model LH-10
≤ (power supply - 10 V) / 0.02 A - (cable length in m x 0.14 Ω)
≤ (power supply - 3 V) / 0.02 A - (cable length in m x 0.14 Ω)
> 100 kΩ
EN
13