Xylem CentriPro AQUAVAR SOLO Manuel D'instructions page 14

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Flashes
Controller Status
3 Blinks
Sensor Fault
The controller will not run
if the signal from the
sensor is disconnected or out
of tolerance. The controller
will automatically restart when
the signal is within tolerance. If
fault persists contact installer.
4 Blinks
Over Current
The controller will try to restart the
motor three times before displaying
this fault. To clear the fault, turn off
power to the controller, wait 1 min-
ute, turn on power to the controller.
If fault persists contact installer.
5 Blinks
Short Circuit
If this fault is detected while
the pump is running, the
controller will attempt to restart
three times before displaying this
fault. To clear the fault, turn off
power to the controller, wait 1 min-
ute, turn on power to the controller.
If fault persists contact installer.
14
Table 5: Fault Blink Codes
RED LIGHT CODES (continued)
Description
This fault can be caused by:
• Disconnected sensor. Disconnect sensor from sensor cable connector and
reconnect to ensure a good connection.
• Disconnected sensor cable lead inside the controller. Check for loose wires
where the sensor cable connects to the circuit board by tugging on each wire.
• Broken wire in the sensor cable.
• Miswired sensor cable. Check that the wires are connected to the correct ter-
minals on the sensor connector. The correct location of the wires is indicated
on the circuit board. B=Black, R=Red, W=White.
• Failed sensor. With the sensor cable connected to the circuit board, measure
the DC voltage between the black and white wires of the sensor cable at
the sensor connector. The voltage measured should be between 0.5Vdc and
4.5Vdc depending on the system pressure, see chart below.
• A vacuum on the sensor (transducer) of 17" Hg or more will cause a sensor
fault, eliminate the vacuum.
5
4.5
4
3.5
3
2.5
2
1.5
1
0.5
0
0
This fault can be caused by:
• Installing wrong motor (wrong voltage or phase).
• Mechanical binding from debris in pump.
• Electrical or mechanical failure of the motor.
• Incorrect setting of "MOTOR OVERLOAD SETTING (SFA)" switch.
A false "over current" error will be displayed if the switch is set too low.
• Pump wire insulation breaking down. Check insulation with megger.
Verify the error by turning power to controller off for 1 minute and then on.
Pump/Motor must be checked if fault persists.
This fault can be caused by:
• Electrical failure of the motor.
• Electrical failure of wiring between controller and motor.
Verify the error by turning power to controller off for 1 minute and then on.
If error persists, motor and wiring between controller and motor must be
checked. Turn power off for 5 minutes. Remove the three motor wires from
the terminal block. Check wiring and motor for shorting phase to phase and
phase to ground. See Section 5 Insulation and Winding Resistance Tests for
details. Refer to motor's manual for information on resistance readings.
(continued on next page)
Sensor Output vs. Applied Pressure
25
50
75
100
Pressure (PSI)
100 PSI Sensor
200 PSI Sensor
125
150
175
200