USAGE AND OPERATION

4.1. The Functions Of The Led Controller

LED srceen
Water flow indication
Press
to set and
check the operation data
Press
to turn on and
turn off the units.

4.2. How To Set Operation Parameter

 Under standby status: press " " button to enter operation
parameter setting interface.
 Press "" or "" to select data for parameters from 0-11.
 Press "MODE" & " " at the same time to start setting
parameters from 0-11, (see operation parameter Table).
 No press in 7seconds, the LED will display water-in
temperature (under running) or "Stby" (when unit stops).
 Under running:
press "" or "" to set the parameter 0 or
1(cooling mode is 0,heating mode is 1).
running, you can press " " to check current
Whilst
parameter, but data cannot be changed. Then press "" ""
can see the parameter from 0-11.
Parameter 1
Parameter 1 to set the entering
water temp. under heating
mode default setting: 27 °C
Parameter 4
Terms of Exit Defrosting
Function default setting: 13°C
Press the key to set the
time to turn on the unit
Parameter 2
Total working time of
compressor after frosting
Parameter 5
Max. Time of defrosting
Default setting: 8min.
8
Defrost indication
Press `MODE` to change
the running mode
Press `CLOCK` to set
the time
Press the key to set the
time to turn off the unit
Parameter 0
to set the entering water
temp. under cooling mode
default setting: 27 °C
Parameter 3
Terms of Entry Defrosting
Function default setting: -7°C
Parameter 6
Compressor number
1 (default) 2