9.4 .Water quality requirements

Irrespective of any legal regulations, the ground water should
not contain any substances that could form deposits. Iron
(< 0.2 mg/l) and Manganese (< 0.1 mg/l) limit values must be
adhered to to prevent iron ochre sedimentation from forming in
the heat source system.
The use of surface water or water containing salt is not permis-
sible. Your local water utility can provide you with general infor-
mation regarding the possible use of ground water. Water anal-
yses are carried out by specially-equipped laboratories.
Irrespective of any legal regulations, a water analysis must be
carried out to establish conclusively whether the ground water
is compatible for the evaporator of a heat pump (see table).
If one characteristic is negative "-" or two characteristics are
"0", the water quality is not sufficient for the heat pump.
If the necessary water quality is not achieved or if this cannot be
guaranteed long-term, we recommended installing a brine-to-
water heat pump equipped with an intermediate circuit.
Table:
Resistance of copper-soldered stainless steel plate heat ex-
changers to substances contained in the water
+
Normally good resistance
0
Corrosion problems can arise,
particularly if several factors receive an evaluation of "0"
-
Should not be used
[<: less than, >: greater than]
Evaluation characteristic
Substances that can settle (org.)
Ammonia NH
3
Chloride
Electrical conductivity
Iron (Fe), dissolved
Free (aggr.) carbonic acid
Manganese (Mn), dissolved
Nitrate (NO
), dissolved
3
PH value
Oxygen
Hydrogen sulphide (H
S)
2
2
HCO
-/SO
-
3
4
Hydrogen carbonate (HCO
-)
3
Aluminium (Al), dissolved
Sulphate
Sulphite (SO
), free
3
Chlorine gas (Cl
)
2
EN-10
Approximate
Evaluation of
concentration
the copper
range (mg/l)
0
< 2
+
2 to 20
0
> 20
-
< 300
+
> 300
0
< 10  S/cm
0
10 to 500  S/cm
+
> 500  S/cm
-
< 0.2
+
> 0.2
0
< 5
+
5 to 20
0
> 20
-
< 0.1
+
> 0.1
0
< 100
+
> 100
0
< 7.5
0
7.5 to 9
+
> 9
0
< 2
+
> 2
0
< 0.05
+
> 0.05
-
> 1
+
< 1
0
< 70
0
70 to 300
+
> 300
0
< 0.2
+
> 0.2
0
< 70
+
70 to 300
0
> 300
-
< 1
+
< 1
+
1 to 5
0
> 5
-
452234.66.74 · FD 9912

10 .Faults / troubleshooting

This heat pump is a quality product and is designed for trouble-
free operation. In the event that a fault should occur, it will be
indicated on the heat pump manager display. In this case, con-
sult the "Faults and troubleshooting" page in the operating in-
structions of the heat pump manager.
If you cannot correct the fault yourself, please contact your
after-sales service technician.
ATTENTION!
Work on the heat pump must only be performed by
authorised and qualified after-sales service technicians!
ATTENTION!
Disconnect all electrical circuits from the power source prior
to opening the device.

11 Decommissioning / disposal

Before removing the heat pump, disconnect it from the power
source and close all valves. The heat pump must be dismantled
by trained personnel. All environmentally-relevant require-
ments regarding the recovery, recycling and disposal of materi-
als and components should be observed in accordance with
the applicable standards. Particular attention should be paid to
the proper disposal of refrigerants and refrigerant oils.