VERTICAL PACKAGED AIR CONDITIONER FEATURING
GAS HEAT AND ELECTRIC COOLING
INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS
This book contains instructions for installation and operation of your unit. Keep it in a safe place for ready reference.
156 Seedling Drive. | Cordele, Georgia 31015 | (229) 273-3636 | www.SuburbanHVACproducts.com
If the information in these instructions are not followed exactly, a fire or explosion may result causing property
damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach a gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal
injury or loss of life. Refer to the installation instructions and/or owners manual provided with this appliance.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
DynaPack
OWNER'S MANUAL
Should you require further information, contact your dealer.
"S" SERIES
DYPA12AC3A036
DYPA12AC3A048
"H" SERIES
DYPA12AC3A039H
Airxcel, Inc. Suburban Applied Products
WARNING
WARNING
STANDARD EFFICIENCY MODELS
DYPA18AC3A036
DYPA24AC3A036
DYPA18AC3A048
DYPA24AC3A048
DYPA18AC3A060
DYPA24AC3A060
HIGH EFFICIENCY MODELS
DYPA18AC3A039H
DYPA24AC3A039H
DYPA18AC3A052H
DYPA24AC3A052H
Manufactured By:
1
Suburban DynaPack S & H Series Owner's Manual 06/2020 Rev.2
COMMERCIAL/INDUSTRIAL GROUP
DYPA30AC3A036
DYPA30AC3A048
DYPA30AC3A060
DYPA30AC3A039H
DYPA30AC3A052H
Part Number 03799

Publicité

Table des Matières
loading

Sommaire des Matières pour Airxcel Suburban DynaPack S Serie

  • Page 1 DYPA24AC3A052H DYPA30AC3A052H Manufactured By: Airxcel, Inc. Suburban Applied Products 156 Seedling Drive. | Cordele, Georgia 31015 | (229) 273-3636 | www.SuburbanHVACproducts.com WARNING If the information in these instructions are not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
  • Page 2: Unit Specifications

    WARNING Installation and servicing of air conditioning equipment can be hazardous due to internal refrigerant pressure and live electrical components. Only trained and qualified service personnel should install or service this equipment. Installation and service performed by unqualified persons can result in property damage, personal injury, or death.
  • Page 3 208/230V 60 Hz 1Ø POWER SUPPLY COMP INDUCER NOTE 2 NOTE 1 230V TRANSFORMER VALVE SPARK IGNITER FLAME SWITCH BLOWER LIMIT HIGH LIMIT SWITCH FLAME 24 VAC UNUSED GROUND ACB HEAT ACB COOL ROLLOUT SWITCH PRESSURE CMB BLOWER SWITCH 1. INTERCHANGE ORANGE AND RED LEADS FOR 208V SUPPLY.
  • Page 4 Chapter 2: Installation 2.1 INSPECTING FOR FREIGHT DAMAGES Your unit was carefully packed in a container which complies with the National Safe Transit Test. This means that the packaged product, with normal handling, will withstand the load conditions encountered in normal transit and in handling. Your unit should be inspected immediately after unpacking to determine if any damage is present due to shipping or handling.
  • Page 5: Top View

    The Dynapack unit is approved for indoor installation only and must be TOP VIEW installed with one of the factory supplied wall sleeves. The unit is intended to 4" MIN. TO DOOR be installed in a closet or equipment room. The unit is certified for 0” clearance to the cabinet sides, cabinet back and the first 3 feet of the supply duct.
  • Page 6 E: INSTALLING AND SECURING UNIT TO WALL SLEEVE Before installing and securing the unit to the wall sleeve, make sure that the proper grille kit is installed. Due to the temperatures of the combustion products released from the gas vent, DynaPack gas package units require the use of an aluminum grille kit (see the Accessories chapter).
  • Page 7: Important

    H: GAS SUPPLY WARNING Any conversion of an S-Series natural gas unit to liquefied petroleum (LP) gas must be done by qualified personnel using a conversion kit available from the manufacturer, following the instructions in the conversion kit, If done improperly, over firing of the burners and improper burner operation can result.
  • Page 8 The Dynapack unit is approved for indoor installation only and must be installed with one of the factory supplied wall sleeves. The unit is intended to be installed in a closet or equipment room. The unit is certified for 0” clearance to the cabinet sides, cabinet back and the first 3 feet of the supply duct.
  • Page 9 D: VENTING The Dynapack unit uses outside air for combustion and vents the exhaust products directly outside. The Dynapack unit cannot be vented with other appliances. The venting system of the Dynapack unit cannot be modified or adjusted in any manner other than what is specified in these instructions.
  • Page 10 F: DUCT WORK The duct work for the dwelling should be designed for the lowest possible static pressure to reduce energy usage and noise. Table 9 at the end of this chapter lists the approximate cfm delivery of the units on each of the indoor blower speeds. Table 5 lists the recommended heating and cooling speeds with its approximate cfm delivery.
  • Page 11: Air Filter

    2.4 AIR FILTER The Dynapack unit is equipped with a permanent, cleanable air filter. This filter can be used if the unit is installed so that the filter is accessible to the homeowner. The permanent filter installed inside the unit must be removed and discarded if a disposable filter is installed in the return air duct.
  • Page 12: Electrical Connections

    WARNING - FIRE OR EXPLOSION HAZARD! Failure to follow the safety warning exactly could result in serious injury, death, or property damage. WARNING Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.
  • Page 13 INDOOR CFM vs STATIC PRESSURE (Dry coil + no air filter) Blower Model Number 0.10" wc 0.15" wc 0.20" wc 0.25" wc 0.30" wc 0.40" wc 0.50" wc 0.60" wc 0.70" wc 0.80" wc Speed MED LO DYPA12AC3A*** MED HI 1060 1050 1042...
  • Page 14: Requirements For Installation

    REQUIREMENTS FOR INSTALLATION Commonwealth of Massachusetts For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied: 1.
  • Page 15 Chapter 3: Unit Startup & Operation WARNING Failure to follow these instructions may lead to a fire, explosion, property damage, personal injury, or loss of life. CAUTION This furnace is equipped with a direct ignition control Do not attempt to manually light the burners. BEFORE OPERATING, smell all around the appliance area for gas.
  • Page 16: System Performance

    10. Your recorded value on input must be within + or- 2% of the rated input. If it is not then adjust the manifold pressure lower to reduce the input or higher to increase the input. Do not go outside of 3.2” to 3.8” water column. 11.
  • Page 17: Heat Exchanger

    Chapter 4: Maintenance WARNING Disconnect all electrical power to the unit before conducting any maintenance procedures. Failure to disconnect the power could result in personal injury or death. 4.1 BURNERS The burners can be removed for cleaning or changing orifices. PLEASE NOTE: This service must be performed by a qualified technician.
  • Page 18 5.2 DYNAPACK WALL SLEEVES REQUIRED WALL OPENING WALL SLEEVE WALL SLEEVE DIMENSIONS Part No. Unit 1736 DYPA30AC3A*** 1737 DYPA30AC3A*** 1738 DYPA30AC3A*** 1739 DYPA30AC3A*** 1740 DYPA30AC3A*** 1741 DYPA12AC3A***, DYPA18AC3A*** and DYPA24AC3A*** 1742 DYPA12AC3A***, DYPA18AC3A*** and DYPA24AC3A*** 1743 DYPA12AC3A***, DYPA18AC3A*** and DYPA24AC3A*** 1744 DYPA12AC3A***, DYPA18AC3A*** and DYPA24AC3A*** 1745...
  • Page 19 Chapter 6: Warranty Airxcel Commercial Group Limited Product Warranty Marvair Inc., warrants its Suburban Applied Products to be free from defects in materials and workmanship under normal use to the original purchaser for the period of time in the table below. If any part of your Suburban AP product fails within 24 months from the date of the original start-up, Marvair will furnish without charge, EXW Cordele, Georgia, the required replacement part.
  • Page 20 APPENDIX A The Dynapack condensate drain system is designed to be installed in a conditioned space. To prevent freezing of the drain condensate in the P-Trap, the installation location should not be exposed to freezing conditions. In installations where the drain system is exposed to freezing conditions, we offer an optional heated P-Trap which is available for purchase.
  • Page 21: Climatiseur Conditionné Verticalement Chauffage Au Gaz Et Refroidissement Électrique

    DYPA24AC3A052H DYPA30AC3A052H Fabricant : Airxcel, Inc. Suburban Applied Products 156 Seedling Drive. | Cordele, Georgia 31015 | (229) 273-3636 | www.SuburbanHVACproducts.com AVERTISSEMENT Si les informations contenues dans ces instructions ne sont pas suivies exactement, un incendie ou une explosion pourrait en résulter, entraînant des dommages matériels, des blessures corporelles ou même la mort.
  • Page 22: Chapitre 1: Description Et Caractéristiques

    AVERTISSEMENT L'installation et l'entretien des équipements de climatisation peuvent être dangereux en raison de la pression interne du réfrigérant et des composants électriques sous tension. Seul un personnel de service formé et qualifié est autorisé à installer ou entretenir cet équipement. L'installation et l'entretien effectués par des personnes non qualifiées peuvent entraîner des dommages matériels, corporels, voire mortels.
  • Page 23: Alimentation

    208/230 V 60 Hz 1Ø ALIMENTATION COMP INDUCTEUR NOTE 2 NOTE 1 230V TRANSFORMATEUR ROBINET À GAZ ALLUMEUR À ÉTINCELLES INTERRUPTEUR DE FLAMME SOUFFLANTE LIMITE INTERRUPTEUR FIN DE COURSE FLAMME 24 V Ca INUTILISÉ TERRE ACB CHAUFFAGE ACB REFROIDISSEMENT 24 V INTERRUPTEUR ROTATIF 24 V...
  • Page 24: Inspection Des Dommages Liés Au Transport

    Chapitre 2 : Installation 2.1 INSPECTION DES DOMMAGES LIÉS AU TRANSPORT Votre appareil a été soigneusement conditionné dans un conteneur conforme au National Safe Transit Test. Ceci signifie que le produit conditionné résistera, sous réserve de manipulation normale, aux conditions de charge rencontrées lors d'un transport normal. Votre appareil doit être inspecté immédiatement après le déballage pour déterminer si des dommages existent, dus à...
  • Page 25: Vue De Dessus

    VUE DE DESSUS Le Dynapack est approuvé uniquement pour installation à l'intérieur avec l'un des caissons muraux fournis par l'usine. L'appareil est prévu pour être installé dans un 4" MIN. À LA PORTE placard ou un local technique. L'unité est certifiée pour un espace libre de 0” sur les côtés et le dos de l'armoire, et les 3 premiers pieds du conduit d'alimentation.
  • Page 26 E : INSTALLATION ET FIXATION DE L'APPAREIL AU CAISSON MURAL Avant d'installer et de sécuriser l'appareil sur le caisson mural, assurez-vous que le kit de grille approprié est installé. En raison de la température des produits de combustion évacués par l'évent de gaz, l'ensemble de gaz du DynaPack nécessite l'utilisation d'un kit de grille en aluminium (voir le chapitre Accessoires).
  • Page 27: Avertissement - Danger D'empoisonnement Au Monoxyde De Carbone

    H : ALIMENTATION EN GAZ AVERTISSEMENT Toute conversion d’un appareil de la Série S du gaz naturel au gaz propane (LP) doit être effectuée par un personnel qualifié, à l’aide d’un kit de conversion disponible auprès du fabricant, en suivant les instructions du kit de conversion. En cas de conversion incorrecte, la surchauffe ou le mauvais fonctionnement des brûleurs peut en résulter.
  • Page 28: B : Installation Du Caisson Mural Et De La Grille

    Le Dynapack est approuvé uniquement pour installation à l'intérieur avec l'un des caissons muraux fournis par l'usine. L'appareil est prévu pour être installé dans un placard ou un local technique. L'unité est certifiée pour un espace libre de 0” sur les côtés et le dos de l'armoire, et les 3 premiers pieds du conduit d'alimentation.
  • Page 29 D : ÉVACUATION Le Dynapack utilise l'air extérieur pour la combustion et évacue les produits d'échappement directement à l'extérieur. Le Dynapack ne peut pas être ventilé avec d'autres appareils. Le système de ventilation du Dynapack ne peut pas être modifié ou ajusté d'une manière quelconque autre que celle qui est spécifiée dans ces instructions.
  • Page 30: G : Drain De Condensats - Refroidissement

    F : CONDUITS Les conduits du logement doivent être conçus pour une pression statique la plus faible possible afin de réduire la consommation d'énergie et le bruit. Le Tableau 9, à la fin de ce chapitre, répertorie le débit approximatif des appareils en cfm à chacune des vitesses de la soufflante intérieure. Le Tableau 5 répertorie les vitesses de chauffage et de refroidissement recommandées avec le débit approximatif en cfm.
  • Page 31: Filtre À Air

    2.4 FILTRE À AIR Le Dynapack est équipé d'un filtre à air permanent et nettoyable. Ce filtre peut être utilisé si l'appareil est installé de manière à ce que le filtre soit accessible au propriétaire. Le filtre permanent installé à l'intérieur de l'unité doit être retiré et mis au rebut si un filtre jetable est installé dans le conduit de retour d'air. La surface de filtre minimale requise pour le Dynapack en fonction de la capacité...
  • Page 32: Raccordements Électriques

    AVERTISSEMENT - RISQUE D'INCENDIE OU D'EXPLOSION! La non-observation exacte de l'avertissement de sécurité peut entraîner des dommages corporels et matériels sérieux, voire mortels. AVERTISSEMENT Ne testez jamais les fuites de gaz avec une flamme nue. Utilisez une solution de savon disponible dans le commerce, spécialement conçue pour la détection des fuites, pour vérifier toutes les connexions.
  • Page 33 CFM INTÉRIEUR vs PRESSION STATIQUE (serpentin sec + pas de filtre à air) Vitesse Numéro de modèle de la 0,10" ce 0,15" ce 0,20" ce 0,25" ce 0,30" ce 0,40" ce 0,50" ce 0,60" ce 0,70" ce 0,80" ce soufflante MOY BAS DYPA12AC3A*** MOY HAUT...
  • Page 34: Exigences Relatives À L'installation

    EXIGENCES RELATIVES À L'INSTALLATION Commonwealth du Massachusetts Pour tous les équipements fonctionnant au gaz, avec évacuation horizontale par un mur latéral, qui sont installés dans chaque habitation, bâtiment ou structure utilisés en tout ou en partie à des fins résidentielles, y compris ceux qui appartiennent au Commonwealth ou sont exploités par ce dernier, et dont la terminaison de l'évent d'évacuation du mur latéral est à...
  • Page 35: Contrôle Du Fonctionnement De L'appareil

    Chapitre 3 : Mise en marche et fonctionnement de l'appareil AVERTISSEMENT Si ces instructions ne sont pas respectées, un incendie, une explosion, des dégâts matériels, corporels, voire mortels risquent de se produire. MISE EN GARDE Cette chaudière est équipée d'un contrôle d'allumage direct. N'essayez pas d'allumer manuellement les brûleurs. AVANT OPÉRATION, sentez le gaz tout autour de l’appareil.
  • Page 36: Réglage Du Refroidissement

    Votre valeur enregistrée pour l'admission doit se trouver à ± 2 % de la valeur assignée. Si ce n'est pas le cas, diminuez la pression du collecteur pour réduire l'admission, ou l'augmenter pour accroître l'admission. Rester dans la limite d'une colonne d'eau de 3,2" à 3,8". Le seul ajustement pour le propane consiste à...
  • Page 37: Chapitre 4 : Entretien

    Chapitre 4 : Entretien AVERTISSEMENT Débranchez toute source d'alimentation électrique de l'appareil avant d'effectuer l'entretien. Laisser l'alimentation branchée peut causer des blessures corporelles graves, voire mortelles. 4.1 BRÛLEURS Les brûleurs peuvent être retirés pour le nettoyage ou le remplacement des orifices. VEUILLEZ NOTER : Ce service doit être effectué...
  • Page 38: Caissons Muraux Pour Dynapack

    5.2 CAISSONS MURAUX POUR DYNAPACK OUVERTURE MURALE REQUISE CAISSON MURAL DIMENSIONS DES CAISSONS MURAUX Réfé- Appareil rence 1736 DYPA30AC3A*** 1737 DYPA30AC3A*** 1738 DYPA30AC3A*** 1739 DYPA30AC3A*** 1740 DYPA30AC3A*** 1741 DYPA12AC3A***, DYPA18AC3A*** et DYPA24AC3A*** 1742 DYPA12AC3A***, DYPA18AC3A*** et DYPA24AC3A*** 1743 DYPA12AC3A***, DYPA18AC3A*** et DYPA24AC3A*** 1744 DYPA12AC3A***, DYPA18AC3A*** et DYPA24AC3A*** 1745...
  • Page 39: Chapitre 6 : Garantie

    Commercial Group diagnostiquera le défaut et, si le défaut est couvert par cette garantie, Airxcel Commercial Group honorera sa garantie et fournira la pièce de rechange requise. Tous les frais d’expédition et les risques de perte lors de l’expédition du produit à Airxcel Commercial Group, et à son retour au propriétaire, incombent au propriétaire.
  • Page 40: Tuyau De Drainage En Caoutchouc (Noir)

    ANNEXE A Le système de drainage des condensats du Dynapack est conçu pour être installé dans un espace climatisé. Pour éviter le gel des condensats de drainage dans le siphon de forme P, l'emplacement de l'installation ne doit pas être exposé au gel. Dans les installations où le système de drainage est exposé au gel, nous proposons en option un siphon de forme P chauffé, disponible à...