F: DUCT WORK
The duct work for the dwelling should be designed for the lowest possible static pressure to reduce energy usage and noise. Table 9 at
the end of this chapter lists the approximate cfm delivery of the units on each of the indoor blower speeds. Table 5 lists the recommended
heating and cooling speeds with its approximate cfm delivery. Use both tables to properly design the duct system for both heating and
cooling cfm.
Model
DYPA12AC3A039H
DYPA18AC3A039H
DYPA18AC3A052H
DYPA24AC3A039H
DYPA24AC3A052H
DYPA30AC3A039H
DYPA30AC3A052H
G: CONDENSATE DRAIN - COOLING
RETURN
SUPPLY
ACCESS PANEL
TO
CONTROLS
ACCESS PANEL
TO GAS VALVE
AND BURNERS
DRAIN TRAP TUBE
ACCESS PANEL
TO COMPRESSOR
AND OUTDOOR FAN
FRONT VIEW
H: CONDENSATE DRAIN - FURNACE
The high efficiency furnace in this unit will produce condensate when operating. In addition, a trap is needed in order to overcome the
negative pressure produced by the combustion inducer blower.
1. With the gas valve and outdoor section access panels removed, connect the drain trap to the internal drain hoses using the 90
degree barb fittings provided.
2. Install the ¾ x ¾ x 5/8 tee fitting in the air conditioner drain at the level of the combustion condensate trap.
3. Complete the furnace drain line by installing a barb fitting into the drain trap hose.
4. Install a 5/8 vinyl hose between the barb fitting and the tee fitting installed in the air conditioner drain line. See Figure 9. The furnace
condensate line will self-prime on startup.
Note: The furnace drain and air conditioner condensate drain are open to the atmosphere which gives pressure equalization on the
sewer trap preventing "double trapping."
I: GAS SUPPLY
All Dynapack H-Series units are built to operate on natural gas only.
Minimum gas supply pressure for purposes of input adjustment:
Natural Gas
*Water Column
Suburban DynaPack S & H Series Owner's Manual 06/2020 Rev.2
Recommended
Heating Speed
high
high
high
high
high
high
high
ELECTRICAL POWER ENTRANCE
FILTER DOOR
GROUND JOINT UNION
(FIELD SUPPLIED)
MANUAL SHUTOFF VALVE
1
WITH
8 "NPT PLUGGED TAPPING,
ACCESSIBLE FOR TEST GAUGE
CONNECTION (FIELD SUPPLIED)
DRIP LEG (FIELD SUPPLIED)
3/4" X 3/4" X 5/8" TEE
CONDENSATE DRAIN
18"
TRAP
ROUTE TO BUILDING DRAIN
Figure 9
Minimum
Maximum
5" W.C.
10" W.C.
Table 6
Approx.
Approx.
CFM
Temp Rise F
1000
35
1000
35
1000
45
1000
35
1000
45
1000
35
1000
45
Table 5
The Dynapack unit and wall sleeve each have their own drain. The unit
drain is for the condensate developed by the evaporator coil. It needs to
be trapped and routed to the building drain system. Use ¾" pvc pipe
and fittings (field supplied).
The wall sleeve is equipped with a drain pan that collects rain water
entering the wall sleeve and the unit condenser coil area. At the time of
installation of the wall sleeve, this drain can be directed directly outside
or turned inside and routed to the building drain system. If the wall
sleeve drain is routed to the building sewer system, then it must be
trapped to prevent sewer gasses from escaping. The top of the sewer
trap must be no higher than 18 inches above the bottom of the furnace.
See Figure 9.
10
Recommended
Approx.
Cooling Speed
CFM
Low
medium low
medium low
medium
medium
medium high
medium high
400
550
550
700
700
900
900