Snmp Configuration; Table 5.5-2: Parameter Table - Enconnex AC6000 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Username
Password
Control
Output Cycle
Time
System
Cycle Power
Clear Faults
5.5.2

SNMP Configuration

The AC6000 has support for SNMP versions 1 through 3. When the AC6000 is configured to work
with SNMPv3, SNMPv1 and v2 SET/GET commands will be ignored. The default username and
password for the SNMPv3 Admin user is Enconnex and ecx@123. The default username and
password for the SNMPv3 Read-Only user is AC6000 and Aes@123. To configure the AC6000 to
work with SNMPv3:
Step 1:​ Set the SNMPv3 Admin Username and Password by issuing a SET command to OID
.1.3.6.1.4.1.52251.2.1.1.4.5 for Username and .1.3.6.1.4.1.52251.2.1.1.4.6 for Password. These
credentials will allow a user to read and write any SNMP field.
Step 2: ​ S et the SNMPv3 Read-Only Username and Password by issuing a SET command to OID
.1.3.6.1.4.1.52251.2.1.1.4.3 for Username and .1.3.6.1.4.1.52251.2.1.1.4.4 for Password. These
credentials will allow a user to have read-access to SNMP fields.
Step 3:​ Set the SNMPv3 authentication protocol by issuing a SET command to OID
.1.3.6.1.4.1.52251.2.1.1.4.1 and the desired authentication protocol: MD5 (1) (default) or SHA (2).
Step 4: ​ Only the Admin or Read-Only user may be configured to receive traps when configured to
SNMPv3. If the Admin user is the intended trap receiver:
i. Set the Admin Message Process Model OID .1.3.6.1.4.1.52251.2.1.1.4.10 to 3.
ii. Set the Admin Security Model OID .1.3.6.1.4.1.52251.2.1.1.4.12 to 3.
iii. Set the Read-Only Message Process Model OID .1.3.6.1.4.1.52251.2.1.1.4.9 to 0 (for v1) or 1
(for v2).
iv. Set the Read-Only Security Model OID .1.3.6.1.4.1.52251.2.1.1.4.11 to 1 (for v1) or 2 (for v2).
admin
User
configurable
admin
User
configurable
1 sec
1 – 20 sec
Off
Off, On

Table 5.5-2: Parameter Table

Sets the username for
access to the AC6000 web
page.
Sets the password for access
to the AC6000 web page.
Sets the amount of time to
shut the output off when
Cycle Power is selected.
Turns the system on or off.
Cycles output power.
Attempts to clear any fault
conditions on the AC6000.
32 